| 40 |
4.5.3 Clearing the analog input configuration
Any analog input configuration settings such as alarm, naming, messaging and scaling can be cleared using the command:
1210,m,n |
|
1210: | Command ID |
m: | Module number (0 for |
| unit, |
n: | Input number |
| unit, |
4.5.4 Setting the analog inputs alarm deadband
A special command is available to configure alarm deadband (hysteresis) for all analog inputs. Alarm deadband is a small range in the total scale of the input signal where alarm states remain indifferent, holding on their last value - in order to avoid frequent SMS transmissions.
The Alarm deadband is given as a percent of the total scale.
1800,d |
|
1800: | Command ID |
d: | Alarm deadband value in % up to 5% of |
| the total scale |
| Example: d =2.3% |