4.6 Special I/O Functions

4.6.1 ON/OFF and PID control

Up to four ON/OFF or PID control function blocks are available. Each block uses an analog input for measuring the process value and a digital output for control.

Function block configuration

1250,id,m,n,m1,n1,sp,g,it,dt,ct,h

1250:

Command ID.

id:

Function block ID (1-4).

m:

Module number (0 for SCOM-100 main

 

unit, 1-4 for AI-4 expansion units).

n:

Input number (1-2 for SCOM-100 main

 

unit, 1-4 for AI-4 expansion units).

m1:

Module number (0 for SCOM-100 main

 

unit, 1-8 for DI-42 I/O expansion units).

n1:

Output number (1-4 for SCOM-100

 

main unit, 1-2 for DI-42 I/O expansion

 

units).

sp:

Set point value in the range of the

 

analog input scale.

g:

‘Gain’ value (P) between 1 and 100%.

 

The block function depends on the

 

‘Gain’ value: A zero value selects the

 

ON/OFF control function. A non zero

 

value selects the PID function.

it:

‘Integral time’ (I) value between 1-1000

 

sec. A zero value disables the integral

 

part (not relevant for ON/OFF control).