SCOM-100, User guide

48

The Status LED switches off and the unit enters the STOP state.

6.2 Controlling the device status

A digital input can be used to switch between RUN and MONITOR mode for power saving purposes.

1105,m,n,v

 

1105:

Command ID

m:

Module number (0 for SCOM-100 main

 

unit, 1-8 for DI-42 I/O expansion units)

n:

DI input number (1-4)

v:

Input state for switching to MONITOR

 

mode (0,1).

The function can be deactivated with the ‘Clear DI configuration command (See 4.3.2).

6.3 Controlling the device response

6.3.1 Send acknowledgement SMS

The device sends a typical acknowledgement response SMS to all configuration commands. The contained text in these SMS can be ‘COMMAND PROCESSED OK’ or ‘OK’ (according to the active answer mode Verbose or Brief) in case of successful command execution or All acknowledgement SMS send by the device can be cancelled using the command:

0621

Note: In the case of a rejected command, the error response SMS is always being sent.

The acknowledgement SMS can be restored using the command:

Page 48