4.5 Analog signal alarming
4.5.1 Analog input configuration
The SCOM-100 analog inputs can be configured to
initiate alarm SMS messages when preset alarm limit
conditions (low & high alarm limits) are met. A user
configurable scale can be defined to associate an analog
input signal to physical units. The configuration command
is:
1200,m,n,s,SSL,SSH,SCL,SCH,ALL,ALH,u,d
1200: Command ID
m: Module number (0 for SCOM-100 main
unit, 1-4 for AI-4 expansion units)
n: Input number (1-2 for SCOM-100 main
unit, 1-4 for AI-4 expansion units)
s: Input signal name (Text: 0-15
characters, may include space
characters)
SSL: Raw value reading for scale low (0-
4095)
SSH: Raw value reading for scale high (0-
4095)
SCL: Scale low in physical units (-100,000 to
100,000)
SCH: Scale high in physical units (-100,000
to 100,000)
ALL: Alarm low limit in physical units
(Number in the range of SCL to SCH
with one optional decimal digit.
Example: ALL = 52.3)