SCOM-100, User guide

42

dt:

‘Derivative time’ (D) value between 1-

 

200 sec. A zero value disables the

 

drivative part (not relevant for ON/OFF

 

control)..

 

ct:

‘Cycle time’ value between 1 and 15

 

minutes, representing the pulse width

 

modulation period of the digital output

 

(not relevant for ON/OFF control).

h:

‘Hysteresis’ value in [%] of the analog

 

input scale (0-20%) for ON/OFF control

 

(not relevant for PID control).

Changing the set point value

1255,id,sp

 

1255:

Command ID.

id:

Function block ID (1-4).

sp:

Set point value in the range of the

 

analog input scale.

Setting the Function block state

The ON/OFF or PID control function block can be enabled or disabled with this SMS command:

1251,id,s

 

1251:

Command ID.

id:

Function block ID (1-4).

s:

1: enable, 0:disable

Controlling the Function block state

A digital input can be configured to control the Enabled/Disabled status of the function block.

The following command selects the digital input.

Page 42
Image 42
Infinite Peripherals SCOM-100 manual 1255,id,sp, 1251,id,s