INSTALLATION / HANDLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA – ALL UNITS SSR UP6–40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard voltage

200V

230V

 

380V

 

460V

 

575V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PACKAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor enclosure

ODP

 

TEFC

ODP

 

TEFC

ODP

 

TEFC

ODP

 

TEFC

ODP

 

TEFC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power (nominal)

 

 

 

 

 

 

 

40HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full load current at maximum

136.0A

 

125.6A

118.3A

 

109.2A

71.6A

 

66.1A

59.2A

 

54.6A

47.3A

 

43.7A

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full load current at maximum

143.7A

 

133.3A

125.2A

 

116.1A

 

62.5A

 

57.9A

 

 

pressure with dryer option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting current FV (STAR)

706.1 (264.5)

614 (230)

367 (135.2)

307 (115)

245.6 (92)

 

 

 

 

 

 

 

 

 

 

 

Starting

current FV (STAR)

744.4 (302.5)

652 (268)

 

323 (131)

 

 

with dryer option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting time FV (STAR)

 

 

 

 

 

 

3–5 Sec (7–10 Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starts per hour (maximum)

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA – FV / Star Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control voltage

 

 

 

 

 

 

120VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum fuse rating

175A

150A

100A

 

90A

 

75A

 

60A

 

See note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum fuse rating with dryer

200A

 

175A

175A

 

150A

 

80A

 

75A

 

 

option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum wire size AWG

 

4/0

 

3/0

 

2

 

3

 

4

 

See note 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA – ALL UNITS SSR UP6 50PE, UP6 50PEI, HF50–PE, EP50–PE, HP50–PE and HXP50–PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard voltage

200V

230V

 

380V

 

460V

 

575V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PACKAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor enclosure

ODP

 

TEFC

ODP

 

TEFC

ODP

 

TEFC

ODP

 

TEFC

ODP

 

TEFC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power (nominal)

 

 

 

 

 

 

 

50HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full load current at maximum

170.8A

 

160.0A

148.5A

 

139.1A

89.8A

 

82.2A

74.2A

 

67.9A

59.4A

 

55.7A

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full load current at maximum

 

155.4A

 

146.0A

 

77.5A

 

71.2A

 

 

pressure with dryer option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting current FV (STAR)

876.3 (321.2)

762 (279.3)

461 (169.0)

381 (139.7)

304.8 (111.7)

 

 

 

 

 

 

 

 

 

 

 

 

Starting

current FV (STAR)

 

800 (317)

 

397 (156)

 

 

with dryer option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting time FV (STAR)

 

 

 

 

 

 

3–5 Sec (7–10 Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starts per hour (maximum)

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA – FV / Star Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control voltage

 

 

 

 

 

 

120VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum fuse rating

225A

 

200A

200A

 

175A

110A

 

110A

100A

 

90A

75A

 

70A

 

See note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum fuse rating with dryer

 

200A

 

200A

 

100A

 

90A

 

 

option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum wire size AWG

 

250

 

4/0

 

1

 

2

 

3

 

See note 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,

http://air.ingersollrand.com

HP50–PE, HXP50–PE

Page 20