Chapter 8 Communication Functions

7) Function code types and memory mapping

 

Code

 

 

Function code name

 

 

Modicon PLC

 

 

Remark

 

 

 

 

 

 

Data address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

 

 

Read Coil Status

 

 

0XXXX(bit-output)

 

 

Read bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

 

 

Read Input Status

 

 

1XXXX(bit-input)

 

 

Read bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

 

 

Read Holding Registers

 

 

4XXXX(word-output)

 

 

Read words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

 

 

Read Input Registers

 

 

3XXXX(word-input)

 

 

Read words

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

 

 

Force Single Coil

 

 

0XXXX(bit-output)

 

 

Write bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

 

 

Preset Single Register

 

 

4XXXX(word-output)

 

 

Write word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

Force Multiple Coils

 

 

0XXXX(bit-output)

 

 

Write bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

Preset Multiple Registers

 

 

4XXXX(word-output)

 

 

Write words

 

 

 

 

 

 

 

 

 

 

 

 

 

MASTER-K120S Mapping

 

Bit area

 

Word area

Address

 

Data area

Address

Data area

h0000

 

P area

h0000

P area

h1000

 

M area

h1000

M area

h2000

 

L area

h2000

L area

h3000

 

K area

h3000

K area

h4000

 

F area

h4000

F area

h5000

 

T area

h5000

T area(current value area)

h6000

 

C area

h6000

C area(current value area)

 

 

 

h7000

S area

 

 

 

h8000

D area

8) Modbus addressing rules

MASTER-K120S main unit starts its address from 0 and matches with 1 of Modicon products' data address. So MASTER- K120S's address n matches n+1 of Modicon products' address. This means that the output contact point 1 (0001) of Modicon products is marked as communication address 0 and the input contact point 1 (0001) of Modicon products is marked as communication address 0 in MASTER-K120S.

9) The size of using data

As for data size, MASTER-K120S main unit supports 128 bytes in ASCII mode and 256 bytes in RTU mode. The maximum size of the Modicon products is different from each other kind. So refer to "Modicon Modbus Protocol Reference Guide."

8-59