Chapter 5 Power Supply / CPU
5- 21

3) Debug operation conditions

following four operation conditions can be specified.
Operation conditions Description
executed by one
command. When executed, Stop operation after executing one instruction
executed by break-point
settings. When executed, Stop operation at designated break-point
executed by the
condition of the device When executed, Stop operation by condition of designated device’s status
executed by the
specified scan time When executed, Operates specified scan time.

4) Operation method

(1) Execute the operation after the debug operation conditions have been set in the KGLWIN.
(2) In interrupt programs, each task can be specified to operation enable/disable.
For detailed operation method, refer to the KGLWIN User’s Manual Chapter 9.
5.5.5 Operation Mode Change

1) Operation mode change methods

The following method is used to change the operation mode.
(1) Change by the mode-setting switch of CPU module.(Standard type only)
(2) Change by the KGLWIN connected with the CPU module communications port.
(3) Change by the KGLWIN connected to the remote CPU module through Cnet I/F
(4) Change by the ‘STOP’ instruction, during program execution.
(5) Change by the KGLWIN connected to the remote CPU module through Fnet(Standard type only)

2) Operation mode change by the mode-setting switch of CPU module.(Standard type only)

The following shows the operation mode change by the mode-setting switch of CPU module.
Mode setting switch position Operation mode
RUN Local RUN
STOP Local STOP
STOP PAU / REM Remote STOP
PAU / REM RUN 1 Local RUN
RUN PAU / REM * 2 Local PAUSE
PAU / REM STOP Local STOP
REMARK
-. If the operation mode changes from RUN mode to local RUN mode by the mode setting switch, the
PLC operates continuously without stopping.