Chapter 7 Usage of Various Functions
7-63
7.2.5 RTD input module(Standard type only)
1) Performance specification
The performance specification of the RTD input module are following.
Item Specification
Connectable RTD Pt 100 (JIS C1640-1989, DIN 43760-1980)
JPt100 (KS C1603-1991, JIS C1604-1981)
Temperature input range Pt 100 : -200 ~ 600 (18.48 to 313.59)
JPt100 : -200 ~ 600 (17.14 to 317.28)
Digital output Digital conversion value : 0 to 4,000
Detected temperature value : -2000 to 6000 (one digit after point * 10)
Burn out detection Each of three wires at every channel has detection function.
Accuracy ±0.5%
[
Full Scale
]
Maximum conversion
speed 40 scan / 1 module
Number of temperature
input device points 4Channel / 1module
Insulation method Photo-coupler insulation between the input terminal and the PLC power
supply (non-insulation between channels)
Connection terminal block 8-point terminal block * 2
Current consumption 25
Voltage DC21.6 26.4V
External power
supply Current 70
Weight 240g
2) Names of parts and functions
No Name Contents
RUN LED Indicate the operating status the G7F-RD2A
RTD input
terminal Terminal which connects Pt100 or JPt100
External power
input terminal External voltage 24VDC needs to this terminal
Extension cable This cable is used to connect while RTD input
module is used
Extension cable
connector
The connector connects extension cable when
extended module is used.
Explain about names of parts and functions
24V
B
A
b
·
B
A
b
·
A
b
B
A
b
24
G
G7F-RD2A
PROGRAMMABLE
LOGIC
CONTROLLER
CH2 CH3
Input
CH0 CH1
PWR
B