7.2.1 A/D·D/A Combination module

1) Performance specification

The performance specification of the analog mixture module are following.

 

Item

 

 

Specifications

 

 

G7F-ADHA

 

G7F-ADHB

 

 

 

 

 

 

Voltage

DC 010V

(input resistance

more than 1 )

 

Input range

 

DC 020 (input resistance 250)

 

Current

DC 420 (input resistance 250)

 

 

 

 

 

Classified by parameter

 

 

Digital output

12Bit( 0~4000)

 

 

Analog Input

 

1.Setting by jumper pin for V/I selection

1.Setting by dipswitch for V/I selection

 

on upper part of product

on left side of product

 

Voltage/Current

 

(Up: voltage, Down: Current)

(Left voltage, Right: Current)

 

selection

 

2. Voltage/current selected by KGLWIN parameter

 

 

 

 

3. When current input is used, short the V and I terminal

 

No. of channel

2 Channels/ 1 module

 

 

 

Absolute max. input

Voltage

DC +12V

 

 

 

Current

DC +24

 

 

 

 

 

 

 

 

Voltage

DC 010V

(External load resistance 2 ㏀∼1 )

 

Output range

Current

DC 020 (External load resistance 510)

 

DC 420 (External load resistance 510)

 

 

 

 

 

Classified by parameter

 

Analog output

Digital Input

12Bit( 0~4000)

 

 

 

Voltage/Current

Separated from terminal

 

 

 

selection

 

 

 

 

 

 

 

 

No. of channel

1Channel / 1 module

 

1Channel / 2 module

 

Absolute max. output

Voltage

DC +12V

 

 

 

Current

DC +24

 

 

 

 

 

 

 

 

Voltage

DC010V : 2.5 (1/4000)

 

 

Max. resolution

Current

DC020 : 5

(1/4000 )

 

 

 

DC420 : 6.25 (1/3200 )

 

Accuracy

±0.5% [Full scale ]

 

 

 

Max. conversion

1 /CH + scan time

 

 

 

speed

 

 

 

 

 

 

 

Common

Isolation

Photo coupler insulation between I/O terminals and PLC power supply

(No isolation between channels)

 

 

 

 

Connect terminal

9 Points terminals *2

 

8 Points terminals *2

 

Internal current

20

 

 

 

 

Consumption

 

 

 

 

 

 

 

 

 

External power

DC 21.6

26.4V

 

 

 

supply

80

 

 

95

 

Weight

240g

 

 

180g

Remark

1)Offset/gain value can’t be changed, it is fixed.

2)Analog inputting is set the current since this is manufactured.

3)Extend to use max.3 Modules

7-40

Page 124