Chapter 7 Usage of Various Functions

7.1.3 Input Filter Function

External input of MASTER-K120S selects input on/off delay time from the range of 0-1000ms of KGLWIN. Credibility secured system may be established by adjustment of input correction no. through using environment.

1) Usage

Input signal status affects to the credibility of system in where noise occurs frequently or pulse width of input signal affects as a crucial factor. In this case the user sets up the proper input on/off delay time, then the trouble by miss operation of input signal may be prevented because the signal which is shorter than set up value is not adopted.

2) Operating Explanation

Input on/off delay time.(filter time)

input signal

input image data

time

input signal

input image data

narrower width pulse than input correction no. is not considered as input signal

3)Using method

(1)Click twice the basic parameter on the project window of KGLWIN.

(2)The value of filter can be set up as one of 0,1,2,5,10,20,50,100,200,500,1000ms to the input on/off delay time of the basic parameter window.(Input on/off delay time is set up as default value of 10ms)

(3)Set up input on/off delay time is conformed to all input is used.

The range of 0-1000ms

7-16