Chapter 7 Usage of Various Functions

 

Error

 

 

Condition

 

 

Operation

 

 

Corrective action

 

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H44

 

POSSOR command can’t be executed during decelerating

 

 

Operating

 

 

Check if positioning is in the decelerating section when POSSOR signal

 

 

 

 

 

 

occur.

 

 

 

 

 

 

 

 

 

 

 

H45

 

POSORG command can’t be executed during operation

 

 

Operating

 

Check if positioning operation is executing when POSORG signal occur.

 

H46

 

 

POSORG command can’t be executed when output is

 

 

Stop

 

 

Check if output is prohibited when POSORG signal occur. Output can be

 

 

 

prohibited

 

 

 

 

enabled by POSCTR command.

 

 

 

 

 

 

 

 

 

 

H47

 

POSCTR setting error

 

-

 

 

Check control command is within 0~3

 

H48

 

Deceleration stop command is available during operating only

 

 

Stop

 

 

Check if positioning operation is not executing when deceleration stop

 

 

 

 

 

 

command occur

 

 

 

 

 

 

 

 

 

 

 

H49

 

POSORG command can’t be executed when JOG operating

 

 

Operating

 

 

Check if JOG operation is executing when deceleration stop command occur

 

H50

 

POSPRS command can’t be executed during operation

 

 

Operating

 

 

Check if positioning operation is executing when POSPRS signal occur

 

H51

 

Direction can’t be changed in continuous operation

 

 

Stop

 

 

Set operation mode as end or keep mode

 

H52

 

Emergency stop error

 

 

Stop

 

 

Remove the causes of emergency stop and clear error by POSCTR

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Get rid of the external upper limit signal range by POSJOG command and

 

H53

 

 

Stroke high limit error

 

 

Stop

 

 

then carry out POSCTR command and clear the error. Output prohibit shall

 

 

 

 

 

 

 

 

 

 

be released by POSCTR command as output prohibit release option

 

 

 

 

 

 

 

 

 

Get rid of the external lower limit signal range by POSJOG command and then

 

H54

 

 

Stroke low limit error

 

 

Stop

 

carry out RST command and clear the error. Output prohibit shall be released

 

 

 

 

 

 

 

 

 

by POSCTR command as output prohibit release option.

 

 

 

 

 

 

 

 

 

 

Install the upper limit detection sensor in the direction that the current

 

H55

 

 

The position of High/Low limit detection Sensor has been changed.

 

 

Stop

 

 

position increases and the lower limit detection sensor in the direction that the

 

 

 

 

 

 

 

 

 

 

current position decreases

7-103