Chapter 10 Maintenance

10-2

10.3 Periodic Inspection

Check the following items once or twice every six months, and perform the needed corrective actions.

Check Items Checking Methods Judgment Corrective Actions

Ambient
temperature 0 ~ 55 °C
Ambient Humidity 5 ~ 95%RH
Ambient
Environment
Ambience
-. Measure with thermometer and
hygrometer
-. measure corrosive gas There should be no
corrosive gases
Adjust to general standard
(Internal environmental standard of
control section)
Looseness, Ingress The module should be move
the unit
The module should be
mounted securely.
PLC
Conditions dust or foreign
material Visual check No dust or foreign material
Retighten screws
Loose terminal
screws Re-tighten screws Screws should not be loose Retighten
Distance between
terminals Visual check Proper clearance Correct
Connecting
conditions
Loose connectors Visual check Connectors should not be
loose.
Retighten connector mounting
screws
Line voltage check Measure voltage between input
terminals
*85 ~ 264V AC
*20~28V DC Change supply power
Fuse Visual check No melting disconnection
If fuse melting disconnection,
change the fuse periodically
because a surge current can cause
heat