Chapter 6 Input and Output Specification
6-11
6.3.3 Expansion Module

1) Specifications

Expansion Module
Model
Specifications G7E-DR10A G7E-DR08A G7E-RY08A G7E-DR20A
Output point 4 points 8 points
Insulation method Relay insulation
Rated load Voltage/current DC24V / 2A (Resistive load), AC220V / 2A (COS Ψ = 1) / 1 point 5A / 1COM
Min. load Voltage/current DC5V / 1mA
Max. load voltage/current AC250V, DC110V
Current leakage when off 0.1mA (AC220V, 60Hz)
Max. on/off frequency 1,200 times/hr
Surge Absorber None
Mechanical More than 20,000,000
Rated on/off voltage/current load 100,000 or more
AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 or more
AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 or more
Life Electrical
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 or more
Off On 10 ms or lower
Response time On Off 12 ms or lower
Operation indication LED is on at on status of output

2) Circuit

It’s the same with the output circuit of the main unit.
3) Output wiring

DC5V
L L L L
DC24V AC110/220V
L L
DC5V/24V AC110/220V