Chapter 6 Input and Output Specification

6.3.3 Expansion Module

1) Specifications

 

Specifications

Model

 

 

 

 

Expansion Module

 

 

 

 

 

G7E-DR10A

 

 

G7E-DR08A

 

 

G7E-RY08A

 

 

G7E-DR20A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output point

 

4 points

 

 

 

8 points

 

 

 

Insulation method

 

 

Relay insulation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated load Voltage/current

 

DC24V / 2A (Resistive load), AC220V / 2A (COS Ψ = 1) / 1 point 5A / 1COM

 

 

 

Min. load Voltage/current

 

DC5V / 1mA

 

 

 

 

 

 

 

 

 

 

Max. load voltage/current

 

AC250V, DC110V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current leakage when off

 

0.1mA (AC220V, 60Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. on/off frequency

 

1,200 times/hr

 

 

 

 

 

 

 

 

 

 

Surge Absorber

 

None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mechanical

 

More than 20,000,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated on/off voltage/current load 100,000 or more

 

 

 

 

 

 

 

Life

 

Electrical

 

AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 or more

 

 

 

 

 

 

AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 or more

 

 

 

Response time

 

Off On

 

10 ms or lower

 

 

 

 

 

 

 

 

 

 

 

On Off

 

12 ms or lower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation indication

LED is on at on status of output

 

 

 

 

 

 

2) Circuit

It’s the same with the output circuit of the main unit.

3)Output wiring

L

L L L

… …

L L

DC5V DC24V

AC110/220V

DC5V/24V AC110/220V

6-11