Chapter 8 Communication Functions
8-21
5) Monitor register(X##)
(1) Introduction
Monitor register can separately register up to 10 in combination with actual variable reading command, and carries out the
registered one through monitor command after registration.
(2) PC request Format
Format name Header Station No. Command Registration No. Registration Format Tail Frame
check
Frame (Example)
ENQ H10 X(x) H09
Refer to registration Format
EOT BCC
ASCII value H05 H3130 H58(78) H3039 [] H04
Item Explanation
BCC When command is lowercase(x), only one lower byte of the value resulted by adding 1 byte
each to ASCII values from ENQ to EOT is converted into ASCII, added to BCC.
Register No. This can be registered up to 10(0 to 9, H00-H09), and if an already registered No. is
registered again, the one currently being executed is registered.
Register Format This is used to before EOT in command of Formats of separate reading of variable,
continuous reading, and named variable reading.
Register Format : Register Format of request Formats must select and use only one of the followings.
Individual reading of device
RSS Number of blocks(2 Byte) Device length (2 Byte) Device name (16 Byte) ...
1 block(max. 16 blocks)
Continuous reading of device
RSB Device length (2 Byte) Device name (16 Byte) Number of data