Chapter 8 Communication Functions

3) Example program 2

It’s supposed that MASTER-K120S main unit is the master and it reads Coil Status of the station no. 17, a Modicon product. The master reads status of the input contact 10197 ~ 10218 of the slave station no. 17.

The input contact of the slave station is supposed to be as follows and the data that are read is saved in M015.

Input

10220

10219

 

 

10218

10217

10216

10215

 

 

10214

10213

10212

10211

 

10210

10209

Status

X

X

 

1

1

0

1

 

0

1

1

1

 

0

1

Hex

 

 

3

 

 

 

 

5

 

 

 

 

D

 

Input

10208

10207

 

 

10206

10205

10204

10203

 

 

10202

10201

10200

10199

 

10198

10197

Status

1

0

 

1

1

1

0

 

1

0

1

1

 

0

0

Hex

 

 

B

 

 

 

A

 

 

 

C

 

The status of input contact 10219,10220 are redundancy.

Data is sent starting from the low bit by byte unit. If the deficient bit of a byte is filled with 0. An example of sending the

above data is as follows. Example 2) AC DB 35

① : It designates slave station and function code ( No. of station : h11(17) , function code : h02 )

: Address setting

Address ‘0’ at MODBUS protocol means address ‘1’ actually .So if you want to designate address ‘10197’ , write address ‘10196’

③ : Reading number setting ( Reading number is 22 from 10197 to 10220.)

④ : This is MODBUS Communication instruction.

The data transmission starts lower byte. The remnant part of byte is filled with ‘0’

Stored data at D200,D201 are :

Device

Stored data

D200

h

AC

DB

D201

h

00

35

8-65

Page 255