Chapter 8 Communication Functions

8.5.2 Communication I/F module

MASTER-K120S series supports various kinds of communication I/F module.

In this time, Built-In Cnet in main unit must be set to ‘Off’ as below and only one communication module can be extended

ON

BUILT_IN CNET

OFF Must be off

ROM MODE

1) Usage of G7L-CUEB

Using G7L-CUEB, MASTER-K120S can connect to other PLC by dedicated modem or dial-up modem

TM/TC Switch

Set TM/TC switch to ‘On’ when uses remote connection function

Set TM/TC switch to ‘Off’ when uses data communication function

Data communication and remote connection function are not allowed simultaneously

Data communication mode supports every communication protocol but In remote connection function supports dedicated protocol only.

2)Usage of G7L-CUEC

Channel 0 can be used as RS-422/485 I/F by using G7L-CUEC I/F module

Operating method is same as built-in Cnet interface and wiring is as below

RDA

RDA

RDA

RDA

 

RDB

RDB

RDB

RDB

 

SDA

SDA

SDA

SDA

 

SDB

SDB

SDB

SDB

Terminating

SG

SG

SG

SG

resistor

Master

 

Slave

Slave

Slave

 

Wiring Example : RS-422 I/F

 

 

 

 

8-76

 

 