• Daisy Chain Connection

Video Multiplexer

Data Multiplex Unit

System Controller

WJ-FS309 (WJ-FS316)

WJ-MP204C

WV-CU360C

Termination:

Termination:

ON

OFF

RS-485

Cable

Branch Cable

DATA

Termination:

ON

RS-485

Cable

DIP Switch Setting (PS Data)

An 8-bit DIP switch mounted on the rear panel specifies the communication mode, etc. The default position is marked with an asterisk *.

OFF

ON

1 2 3 4 5 6 7 8

MODE

 

 

 

 

 

 

 

 

 

Function

 

SW position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 8

Data transmission mode

Fixed to OFF*

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 7

Baud rate selection

Fixed to OFF*

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 6

Operation mode

Operator*

 

Administrator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 5

Line termination

Off

 

On*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

Reserved

Fixed to OFF*

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 3

System Unit Version

Fixed to OFF*

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2

System Unit Version

Fixed to OFF*

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

System Unit Version

Fixed to OFF*

 

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Remove the DC plug from the rear of the controller.

2.Set the switch referring to the table.

3.Connect the DC plug to the controller.

Notes:

Bits 1 - 4 are reserved.

Bit 5 opens or terminates the communication chain. The switch should be set to OFF when the controller is located in an intermediate position.

Bit 6 specifies the operation mode, Operator or Administrator. The switch should be set to Administrator when setting up the controller. Remember to set this switch to the right position after completion of the setup operation.

Bits 7 and 8 are used in the OFF position.