Appendix D—Advanced Power Quality Evaluations

EN50160:2000 Specification

EN50160:2000 “Voltage characteristics of electricity supplied by public distribution systems” is a European standard that defines the quality of the voltage a customer can expect from the electric utility. Although this is a European standard, it can be applied globally.

The PM850 and the PM870 evaluates the following electrical characteristics in accordance with EN50160:

Table D–5: EN50160 Evaluation for the PM850 and PM870

Feature

PM850

PM870

Evaluation During Normal Operation (Meter-based Data)

 

Frequency

3

3

Supply voltage variations

3

3

Supply voltage unbalance

3

3

Harmonic voltage

3

3

Total Harmonic Distortion

3

3

Evaluations During Abnormal Operations (Alarm-based Data)

 

Magnitude of rapid voltage changes

3

3

Supply voltage dips

3

3

Short interruptions of the supply voltage

3

3

Long interruptions of the supply voltage

3

3

Temporary power frequency over-voltages

3

3

The PM850 performs EN50160 evaluations based on standard alarms, while the PM870 performs EN50160 evaluations on disturbance alarms.

These features must be configured using register writes. See Table D–11 on page 99 for a list of configuration and status registers.

As illustrated in Table D–5,the EN50160 evaluations performed by the PM850 and the PM870 can be divided into two categories. The first category performs evaluations during normal operation utilizing meter data. The second category performs evaluations during abnormal operation utilizing either standard alarms (PM850) or disturbance alarms (PM870).

The EN50160:2000 Specification sets limits for most of the evaluations. These limits are built into the PM850 and the PM870 firmware. You can configure registers for other evaluations and change them from the default values.

How Evaluation Results Are Reported

The PM850 and the PM870 reports evaluation data in register entries and alarm log entries. Table D–6describes the register entries for the evaluation data.

Table D–6: Register Entries

Register

Description

Number

 

3910

Summary bitmap of active evaluations that reports which areas

of evaluation are active in the PM850 and the PM870.

 

3911

Summary bitmap of evaluation status that reports the pass/fail

status of each area of evaluation.

 

 

Detail bitmap of evaluation status that reports the pass/fail status

 

of the evaluation of each individual data item. Detailed data

Portal registers

summary information is also available for each of the evaluations

for the present interval and for the previous interval. You can

 

access this data over a communications link using Modbus block

 

reads of “portal” registers. Refer to “Evaluation During Normal

 

Operation” on page 96 for additional information.

Log entries for the evaluation data include:

On-board alarm log entry for diagnostic alarms: When the status of an area of evaluation is outside the range of acceptable values, an entry is made in the on-board alarm log. This entry provides notification of the exception for a specific area of evaluation. This notification is reported only in PowerLogic software and does not appear on the local display.

© 2011 Schneider Electric. All Rights Reserved.

95