PowerLogicTM Series 800 Power Meter

3/2011

Chapter 3—Operation

ALARM (Alarms) Setup

There is an extensive list of meter error conditions which can be monitored and cause an alarm.

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ALARM is visible.

3.Press ALARM.

4.Press <- or ->to select the alarm option you want to edit.

5.Press EDIT.

6.Select to ENABL (enable) or DISAB (disable) the alarm.

7.Press OK.

8.Select the PR (priority): NONE, HIGH, MED, or LOW.

9.Press OK.

10.Select how the alarm values are displayed: ABSOL (absolute value) or RELAT (percentage relative to the running average).

11.Enter the PU VALUE (pick-up value).

12.Press OK.

13.Enter the PU DELAY (pick-up delay).

14.Press OK.

15.Enter the DO VALUE (drop-out value).

16.Press OK.

17.Enter the DO DELAY (drop-out delay).

18.Press OK.

19.Press 1; to return to the alarm summary screen.

20.Press 1; to return to the SETUP MODE screen.

21.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

22.Press YES to save the changes.