PowerLogicTM Series 800 Power Meter

63230-500-225A2

Appendix A—Instrument Transformer Wiring: Troubleshooting Tables

3/2011

Section I: Common Problems for 3-Wire and 4-Wire Systems

Section I—Case A

Symptoms: 3-Wire and 4-Wire

Possible Causes

 

 

 

CT secondaries shorted.

Zero amps

Less than 2% load on power meter based on CT ratio.

 

Zero kW, kVAR, kVA

Example: with 100/5 CT's, at least 2A must flow through CT window for power

 

meter to “wake up.”

 

 

Section I—Case B

Symptoms: 3-Wire and 4-Wire

Possible Causes

 

 

Negative kW of expected magnitude

All three CT polarities backwards; could be CTs are physically mounted

with primary polarity mark toward the load instead of toward source or

Positive kVAR

secondary leads swapped.

 

Normal lagging power factor

All three PT polarities backwards; again, could be on primary or secondary.

NOTE: Experience shows CTs are usually the problem.

 

 

 

Section I—Case C

Symptoms: 3-Wire and 4-Wire

Possible Causes

 

 

 

PTs primary and/or secondary neutral common not grounded (values as

Frequency is an abnormal value; may or may

high as 275 Hz and as low as 10 Hz have been seen).

 

not be a multiple of 50/60 Hz.

System grounding problem at the power distribution transformer (such as

 

 

utility transformer), though this is not likely.

 

 

74

© 2011 Schneider Electric All Rights Reserved

Page 82
Image 82
Schneider Electric PM810 manual Section I Common Problems for 3-Wire and 4-Wire Systems, Section I-Case a, Section I-Case B