63230-500-225A2

PowerLogicTM Series 800 Power Meter

3/2011

 

 

Chapter 1—Introduction

Features

 

 

 

 

 

 

 

Table 1–7: Series 800 Power Meter Features

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM810

PM820

PM850

PM870

 

 

True rms metering to the 63rd harmonic

(3)

(3)

 

 

 

 

 

 

 

 

 

Accepts standard CT and PT inputs

 

 

 

 

 

 

 

 

 

600 volt direct connection on voltage inputs

 

 

 

 

 

 

 

 

 

High accuracy — 0.075% current and voltage (typical conditions)

 

 

 

 

 

 

 

 

 

Min/max readings of metered data

 

 

 

 

 

 

 

 

 

Input metering (five channels) with PM8M22, PM8M26, or PM8M2222

 

 

installed

 

 

 

 

 

 

 

 

Power quality readings — THD

 

 

 

 

 

 

 

 

 

Downloadable firmware

 

 

 

 

 

 

 

 

 

Easy setup through the integrated or remote display (password protected)

 

 

 

 

 

 

 

 

 

Setpoint-controlled alarm and relay functions

 

 

 

 

 

 

 

 

 

On-board alarm logging

 

 

 

 

 

 

 

 

 

Wide operating temperature range: –25° to +70°C for the power meter

 

 

unit

 

 

 

 

 

 

 

 

Communications:

 

 

 

 

 

 

On-board: one Modbus RS485 (2-wire)

 

 

PM8RD: one configurable Modbus RS232/RS485 (2- or 4-wire)

 

 

 

 

 

 

 

 

 

Active energy accuracy: ANSI C12.20 Class 0.2S and IEC 62053-22

 

 

Class 0.5S

 

 

 

 

 

 

 

 

Non-volatile clock

(1)

 

 

 

 

 

 

 

 

 

On-board data logging

(2)

80 KB

800 KB

800 KB

 

 

 

 

 

 

 

 

 

Real-time harmonic magnitudes and angles (I and V):

 

 

 

 

 

 

To the 31st harmonic

(3)

 

 

To the 63rd harmonic

 

 

 

 

 

 

 

 

 

 

Waveform capture

 

 

 

 

 

 

Standard

 

 

Advanced

 

 

 

 

 

 

 

 

 

EN50160 evaluations

 

 

 

 

 

 

NOTE: The PM850 performs EN50160 evaluations based on

 

 

standard alarms, while the PM870 performs EN50160 evaluations

 

 

 

 

 

 

based on disturbance alarms.

 

 

 

 

 

 

ITI (CBEMA) and SEMI-F47 evaluations

 

 

 

 

 

 

NOTE: The PM870 performs ITI (CBEMA) and SEMI-F47

 

 

evaluations based on disturbance alarms.

 

 

 

 

 

 

Current and voltage sag/swell detection and logging

 

 

 

 

 

 

 

 

(1)The Time Clock in the PM810 with PM810LOG is non-volatile. However, it is volatile in the PM810.

(2)The on-board data logging memory in the PM810 with PM810LOG is 80 KB, but it is not available in the PM810.

(3)The PM810 with PM810LOG and the PM820 monitor distortion to the 31st harmonic. Harmonic distortion is not monitored in the PM810.

Firmware

This user guide is written to be used with firmware version 11.xx and above. See “Identifying the Firmware Version, Model, and Serial Number” on page 70 for instructions on how to determine the firmware version. To download the latest firmware version, follow the steps below:

1.Using a web browser, go to http://www.Schneider-Electric.com.

2.Locate the Search box in the upper right corner of the home page.

3.In the Search box enter “PM8”.

4.In the drop-down box click on the selection “PM800 series”.

5.Locate the downloads area on the right side of the page and click on “Software/Firmware”.

6.Click on the applicable firmware version title (i.e. “PowerLogic Series 800 Power Meter Firmware version 12.100”).

7.Download and run the “xxx.exe” firmware upgrade file provided.

© 2011 Schneider Electric. All Rights Reserved.

7

Page 13
Image 13
Schneider Electric PM810 manual Firmware, Series 800 Power Meter Features, PM820 PM850 PM870