63230-500-225A2

 

 

 

PowerLogicTM Series 800 Power Meter

3/2011

 

 

 

Appendix C—Using the Command Interface

 

Table C–2: Command Codes

 

 

 

 

 

 

 

 

 

 

 

 

Command

Command

 

 

 

 

 

Parameter

Parameters

 

Description

 

 

Code

 

 

 

Register

 

 

 

 

 

 

 

 

 

 

 

Resets

 

 

 

 

 

 

 

 

 

 

 

1522

None

None

Resets the alarm history log.

 

 

 

 

 

 

 

 

 

 

0 = Present and previous

 

 

 

4110

8001

months

Resets min/max.

1 = Present month

 

 

 

 

 

 

 

 

 

2 = Previous month

 

 

 

 

 

 

 

 

 

5110

None

None

Resets all demand registers.

 

 

 

 

 

 

5111

None

None

Resets current demand.

 

 

 

 

 

 

5113

None

None

Resets power demand.

 

 

 

 

 

 

5114

None

None

Resets input demand.

 

 

 

 

 

 

5115

None

None

Resets generic demand for first group of 10

quantities.

 

 

 

 

 

5210

None

None

Resets all min/max demand.

 

 

 

 

 

 

5211

None

None

Resets current min/max demand.

 

 

 

 

 

 

5213

None

None

Resets power min/max demand.

 

 

 

 

 

 

5214

None

None

Resets input min/max demand.

 

 

 

 

 

 

5215

None

None

Resets generic 1 min/max demand.

 

 

 

 

 

 

 

 

 

 

Start new demand interval.

 

 

 

 

Bit 0 = Power Demand

5910

8001

Bitmap

1 = Current Demand

 

 

 

 

2 = Input Metering Demand

 

 

 

 

3 = Generic Demand Profile

 

 

 

 

 

 

 

 

 

 

Preset Accumulated Energies

 

 

 

 

Requires the IO Data Pointer to point to

6209

8019

I/O Data Pointer

registers where energy preset values are

 

 

 

 

entered. All Accumulated energy values must

 

 

 

 

be entered in the order in which they occur in

 

 

 

 

registers 1700 to 1727.

 

6210

None

None

Clears all energies.

 

 

 

 

 

 

6211

None

None

Clears all accumulated energy values.

 

 

 

 

 

 

6212

None

None

Clears conditional energy values.

 

 

 

 

 

 

6213

None

None

Clears incremental energy values.

 

 

 

 

 

 

6214

None

None

Clears input metering accumulation.

 

 

 

 

 

 

 

 

 

 

Resets the following parameters to IEEE or

 

 

 

 

IEC defaults:

 

 

 

1 = IEEE

1.

Phase labels

6215

None

2.

Menu labels

2 = IEC

 

 

 

3.

Harmonic units

 

 

 

 

4.

PF sign

 

 

 

 

5.

THD denominator

 

 

 

 

6.

Date Format

 

 

6320

None

None

Disables conditional energy accumulation.

 

 

6321

None

None

Enables conditional energy accumulation.

 

6910

None

None

Starts a new incremental energy interval.

 

Files

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Triggers data log entry. Bitmap where Bit 0 =

7510

8001

1–3

Data Log 1, Bit 1 = Data Log 2, Bit 2 = Data

 

 

 

 

Log 3, etc.

 

 

7511

8001

File Number

Triggers single data log entry.

 

You must write to register 8001 the number that identifies which output you would like to use. To determine the identifying number, refer to“I/O Point Numbers” on page 86 for instructions.

Data buffer location (register 8019) is the pointer to the first register where data will be stored. By default, return data begins at register 8020, although you can use any of the registers from 8020–8149. Take care when assigning pointers. Values may be corrupted if two commands are using the same register.

Refer to “Register List Access” on page 79 for instructions on accessing the complete register list.