Chapter 4—Metering Capabilities

Block Interval Demand

In the block interval demand method, you select a “block” of time that the power meter uses for the demand calculation. You choose how the power meter handles that block of time (interval). Three different modes are possible:

Sliding Block. In the sliding block interval, you select an interval from 1 to 60 minutes (in 1-minute increments). If the interval is between 1 and 15 minutes, the demand calculation updates every 15 seconds. If the interval is between 16 and 60 minutes, the demand calculation updates every 60 seconds. The power meter displays the demand value for the last completed interval.

Fixed Block. In the fixed block interval, you select an interval from 1 to 60 minutes (in 1-minute increments). The power meter calculates and updates the demand at the end of each interval.

Rolling Block. In the rolling block interval, you select an interval and a sub-interval. The sub-interval must divide evenly into the interval. For example, you might set three 5-minute sub-intervals for a 15-minute interval. Demand is updated at each sub- interval. The power meter displays the demand value for the last completed interval.

Figure 4–4below illustrates the three ways to calculate demand power using the block method. For illustration purposes, the interval is set to 15 minutes.

Figure 4–4: Block Interval Demand Examples

 

Calculation updates

 

 

 

 

 

 

 

Demand value is the

 

every 15 or 60

 

 

 

 

 

 

 

average for the last

 

seconds

15-minute interval

 

 

completed interval

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 30 45 60 . . .

 

 

 

 

 

 

 

 

 

 

 

 

(sec)

Sliding Block

 

 

 

Demand value is

 

Calculation updates at

 

the average for

 

the end of the interval

 

the last

 

 

 

completed

 

 

 

interval

15-minute interval

15-minute interval

 

15-min

 

 

 

Time

15

30

45

(min)

 

 

Fixed Block

 

 

Calculation updates at the end of

 

Demand value is

 

the sub-interval (5 minutes)

 

the average for

 

 

the last

 

 

completed

15-minute interval

 

interval

 

 

 

 

 

 

 

 

 

 

Time

PLSD110131

15

20

25

30

35

40

45

(min)

 

 

 

 

 

 

 

 

 

Rolling Block

 

 

 

© 2011 Schneider Electric. All Rights Reserved.