PowerLogicTM Series 800 Power Meter

63230-500-225A2

Chapter 4—Metering Capabilities

3/2011

Min/Max Values for Real-time Readings

When certain one-second real-time readings reach their highest or lowest value, the power meter saves the values in its non-volatile memory. These values are called the minimum and maximum (min/max) values.

The power meter stores the min/max values for the current month and previous month. After the end of each month, the power meter moves the current month’s min/max values into the previous month’s register space and resets the current month’s min/max values. The current month’s min/max values can be reset manually at any time using the power meter display or PowerLogic software. After the min/max values are reset, the power meter records the date and time. The real-time readings evaluated are:

Min/Max Voltage L-L

Min/Max Reactive Power Total

Min/Max Voltage L-N

Min/Max Apparent Power Total

Min/Max Current

Min/Max THD/thd Voltage L-L

Min/Max Voltage L-L, Unbalance

Min/Max THD/thd Voltage L-N

Min/Max Voltage L-N, Unbalance

Min/Max THD/thd Current

Min/Max Total True Power Factor

Min/Max Frequency

Min/Max Total Displacement Power

Min/Max Voltage N-ground

 

Factor

 

(see the note below)

Min/Max Real Power Total

Min/Max Current, Neutral

 

 

 

(see the note below)

NOTE: Min/Max values for Vng and In are not available from the display. Use the display to read registers (see “Read and Write Registers” on page 26) or use PowerLogic software.

For each min/max value listed above, the power meter records the following attributes:

Date/Time of minimum value

Date/Time of maximum value

Minimum value

Maximum value

Phase of recorded minimum value

Phase of recorded maximum value

NOTE: Phase of recorded min/max only applies to multi-phase quantities.

NOTE: There are two ways to view the min/max values. 1- Use the power meter display to view the min/max values since the meter was last reset. 2- Use PowerLogic software to view a table with the instantaneous min/max values for the current and previous months.

Power Factor Min/Max Conventions

All running min/max values, except for power factor, are arithmetic minimum and maximum values. For example, the minimum phase A-B voltage is the lowest value in the range 0 to 1200 kV that has occurred since the min/max values were last reset. In contrast, because the power factor’s midpoint is unity (equal to one), the power factor min/max values are not true arithmetic minimums and maximums. Instead, the minimum value represents the measurement closest to -0 on a continuous scale for all real-time readings -0 to 1.00 to +0. The maximum value is the measurement closest to +0 on the same scale.

Figure 4–1shows the min/max values in a typical environment in which a positive power flow is assumed. In the figure, the minimum power factor is -0.7 (lagging) and the maximum is 0.8 (leading). Note that the minimum power factor need not be lagging, and the maximum power factor need not be leading. For example, if the power factor values ranged from -0.75 to -0.95, then the minimum power factor would be -0.75 (lagging) and the maximum power factor would be -0.95 (lagging). Both would be negative. Likewise, if the power factor ranged from +0.9 to +0.95, the minimum would be +0.95 (leading) and the maximum would be +0.90 (leading). Both would be positive in this case.

28

© 2011 Schneider Electric. All Rights Reserved.

Page 34
Image 34
Schneider Electric PM810, PM870, PM820, PM850 manual Power Factor Min/Max Conventions, Min/Max Values for Real-time Readings