PowerLogicTM Series 800 Power Meter

63230-500-225A2

Chapter 7—Logging

3/2011

Data Logs

The PM810 with a PM810LOG records and stores readings at regularly scheduled intervals in one independent data log. This log is preconfigured at the factory. You can accept the preconfigured data log or change it to meet your specific needs. You can set up the data log to store the following information:

The PM820 records and stores readings at regularly scheduled intervals in one independent data log. The PM850 and PM870 record and store meter readings at regularly scheduled intervals in up to three independent data logs. Some data log files are preconfigured at the factory. You can accept the preconfigured data logs or change them to meet your specific needs. You can set up each data log to store the following information:

Timed Interval—1 second to 24 hours for Data Log 1

Timed Interval—1 second to 24 hours for Data Log 1, and 1 minute to 24 hours for Data Logs 2, 3 and 4 (how often the values are logged)

First-In-First-Out (FIFO) or Fill and Hold

Values to be logged—up to 96 registers along with the date and time of each log entry

START/STOP Time—each log has the ability to start and stop at a certain time during the day

The default registers for Data Log 1 are listed in Table 7–5below.

Table 7–5: Default Data Log 1 Register List

Description

Number of

Data Type

Register Number

Registers

 

 

 

Start Date/Time

3

D/T

Current D/T

 

 

 

 

Current, Phase A

1

integer

1100

 

 

 

 

Current, Phase B

1

integer

1101

 

 

 

 

Current, Phase C

1

integer

1102

 

 

 

 

Current, Neutral

1

integer

1103

 

 

 

 

Voltage A-B

1

integer

1120

 

 

 

 

Voltage B-C

1

integer

1121

 

 

 

 

Voltage C-A

1

integer

1122

 

 

 

 

Voltage A-N

1

integer

1124

 

 

 

 

Voltage B-N

1

integer

1125

 

 

 

 

Voltage C-N

1

integer

1126

 

 

 

 

True Power Factor, Phase A

1

signed integer

1160

 

 

 

 

True Power Factor, Phase B

1

signed integer

1161

 

 

 

 

True Power Factor, Phase C

1

signed integer

1162

 

 

 

 

True Power Factor, Total

1

signed integer

1163

 

 

 

 

Last Demand, Current,

1

integer

2000

3-Phase Average

 

 

 

Last Demand, Real Power,

1

integer

2150

3-Phase Total

 

 

 

Last Demand, Reactive

1

integer

2165

Power, 3-Phase Total

 

 

 

Last Demand, Apparent

1

integer

2180

Power 3-Phase Total

 

 

 

Refer to Appendix A for more information about data types.

Use PowerLogic software to clear each data log file, independently of the others, from the power meter’s memory. For instructions on setting up and clearing data log files, refer to the PowerLogic software online help or documentation.

60