PowerLogicTM Series 800 Power Meter

63230-500-225A2

Appendix A—Instrument Transformer Wiring: Troubleshooting Tables

3/2011

Field Example

Readings from a 4-wire system

kW= 25

kVAR= 15

kVA= 27

IA= 904A

IB= 910A

IC= 931A

I3ΦAvg= 908A

VAB= 495V

VBC= 491V

VCA= 491V

VAN= 287V

VBN= 287V

VCN= 284V

PF3ΦAvg= 0.75 lag to 0.22 lead fluctuating

Troubleshooting Diagnosis

Power factors cannot be correct .

None of the “Section II” symptoms exist, so proceed to the 4-wire troubleshooting (“Section IV”).

Cannot calculate kW because 3-phase power factor cannot be right, so calculate kVA instead.

Calculated kVA = ( 3 × Vab × I3ΦAvg ) ⁄ 1000

=(1.732 × 495 × 908 ) ⁄ 1000

=778 kVA

Power meter reading is essentially zero compared to this value.

4-wire Case E looks similar.

Since the PTs were connected to other power meters which were reading correctly, suspect two CT leads swapped.

Since A-phase power factor is the only one that has a normal looking lagging value, suspect B and C-phase CT leads may be swapped.

After swapping B and C-phase CT leads, all readings went to the expected values; problem solved.

78

© 2011 Schneider Electric All Rights Reserved

Page 86
Image 86
Schneider Electric PM810, PM870, PM820, PM850 manual Field Example, Readings from a 4-wire system, Troubleshooting Diagnosis