PowerLogicTM Series 800 Power Meter

63230-500-225A2

Chapter 3—Operation

3/2011

E-INC (Incremental Energy Interval) Setup

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ADVAN (advanced setup) is visible.

3.Press ADVAN.

4.Press ###: until E-INC (incremental energy) is visible.

5.Press E-INC.

6.Enter the INTVL (interval). Range is 00 to 1440.

7.Press OK.

8.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

9.Press YES to save the changes.

PLSD110197

THD Calculation Setup

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ADVAN (advanced setup) is visible.

3.Press ADVAN.

4.Press ###: until THD is visible.

5.Press THD.

6.Select the THD calculation: FUND or RMS.

7.Press OK.

8.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

9.Press YES to save the changes.

PLSD110206

VAR/PF Convention Setup

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ADVAN (advanced setup) is visible.

3.Press ADVAN.

4.Press ###: until PF is visible.

5.Press PF.

6.Select the Var/PF convention: IEEE or IEC.

7.Press OK.

8.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

9.Press YES to save the changes.

PLSD110209