PowerLogicTM Series 800 Power Meter

 

 

63230-500-225A2

Appendix C—Using the Command Interface

 

 

3/2011

 

Table C–2: Command Codes

 

 

 

 

 

 

 

 

 

 

Command

Command

 

 

 

 

Parameter

Parameters

Description

 

 

Code

 

 

Register

 

 

 

 

 

 

 

 

 

Setup

 

 

 

 

 

9020

None

None

Enter into setup mode.

 

 

 

 

 

 

 

9021

8001

1 = Save

Exit setup mode and save all changes.

2 = Do not save

 

 

 

 

 

 

 

 

 

 

 

You must write to register 8001 the number that identifies which output you would like to use. To determine the identifying number, refer to“I/O Point Numbers” on page 86 for instructions.

Data buffer location (register 8019) is the pointer to the first register where data will be stored. By default, return data begins at register 8020, although you can use any of the registers from 8020–8149. Take care when assigning pointers. Values may be corrupted if two commands are using the same register.

Refer to “Register List Access” on page 79 for instructions on accessing the complete register list.

I/O Point Numbers

All inputs and outputs of the power meter have a reference number and a label that correspond to the position of that particular input or output.

The reference number is used to manually control the input or output with the command interface.

The label is the default identifier that identifies that same input or output. The label appears on the display, in PowerLogic software, and on the option card.

See Table C–3for a complete list of I/O Point Numbers

Table C–3: I/O Point Numbers

Module

Standard I/O

PM8M22

PM8M26

PM8M2222

I/O Point Number

KY

1

S1

2

 

 

 

 

 

 

 

A-R1

A-R1

3

 

 

A-R1

A-R2

A-R2

4

 

 

A-S1

A-S1

5

A

A-R2

A-S2

A-S2

6

A-S1

A-S3

A-AI1

7

 

 

 

 

A-S2

A-S4

A-AI2

8

 

 

 

A-S5

A-AO1

9

 

 

 

A-S6

A-AO2

10

 

 

 

B-R1

B-R1

11

 

 

 

B-R2

B-R2

12

 

 

B-R1

B-S1

B-S1

13

B

B-R2

B-S2

B-S2

14

B-S1

B-S3

B-AI1

15

 

 

 

 

B-S2

B-S4

B-AI2

16

 

 

 

B-S5

B-AO1

17

 

 

 

B-S6

B-AO2

18

Operating Outputs from the Command Interface

To operate an output from the command interface, first identify the relay using the I/O point number. Then, set the output to external control. For example, to energize output 1, write the commands as follows:

1.Write number 1 to register 8001.

2.Write command code 3310 to register 8000 to set the relay to external control.

3.Write command code 3321 to register 8000.

If you look in the “Relay Outputs” section of Table C–2 on page 84, you’ll see that command code 3310 sets the relay to external control and command code 3321 is listed as the command used to energize a relay. Command codes 3310–3381 are for use with inputs and outputs.

Refer to “Register List Access” on page 79 for instructions on accessing the complete register list.

86

© 2011 Schneider Electric. All Rights Reserved.

Page 94
Image 94
Schneider Electric PM810, PM870, PM820, PM850 manual Operating Outputs from the Command Interface, Point Numbers, Setup