63230-500-225A2

PowerLogicTM Series 800 Power Meter

3/2011

Chapter 3—Operation

Power Meter Resets

The Power Meter Resets Feature set contains several items. After resetting a feature, you may continue through the remaining features by returning to the RESET MODE screen and pressing ###: to scroll to additional features. Once you have reset the specific features, press 1; until the display returns to the main screen.

Initialize the Power Meter

Initializing the power meter resets the energy readings, minimum/maximum values, and operating times. To initialize the power meter, follow these steps:

1.Press ###: to scroll through the Level 1 menu until you see MAINT.

2.Press MAINT.

3.Press RESET.

4.Press ###: until METER is visible.

5.Press METER.

6.Enter the password (the default is 0000).

7.Press YES to initialize the power meter and to return to the RESET MODE screen.

8.At the RESET MODE screen, continue resetting additional features or press1; until you return to the main screen.

NOTE: We recommend initializing the power meter after you make changes to any of the following: CTs, PTs, frequency, or system type.

Accumulated Energy Readings Reset

PLSD110285

1.

Press ###: to scroll through the Level 1 menu

 

 

until you see MAINT.

 

2.

Press MAINT.

 

3.

Press RESET.

 

4.

Press ###: until ENERG is visible.

 

5.

Press ENERG.

 

6.

Enter the password (the default is 0000).

 

7.

Press YES to reset the accumulated energy

 

 

readings and to return to the RESET MODE

 

 

screen.

PLSD110280

 

 

© 2011 Schneider Electric. All Rights Reserved.

23

Page 29
Image 29
Schneider Electric PM820, PM870, PM810 Power Meter Resets, Initialize the Power Meter, Accumulated Energy Readings Reset