PowerLogicTM Series 800 Power Meter

63230-500-225A2

Chapter 6—Alarms

3/2011

Alarm Levels

Using PowerLogic software with a PM850 or PM870, multiple alarms can be set up for one particular quantity (parameter) to create alarm “levels”. You can take different actions depending on the severity of the alarm.

For example, you could set up two alarms for kW Demand. A default alarm already exists for kW Demand, but you could create another custom alarm for kW Demand, selecting different pickup points for it. The custom kW Demand alarm, once created, will appear in the standard alarm list. For illustration purposes, let’s set the default kW Demand alarm to 120 kW and the new custom alarm to 150 kW. One alarm named kW Demand ; the other kW Demand 150kW as shown in Figure 6–3.If you choose to set up two alarms for the same quantity, use slightly different names to distinguish which alarm is active. The display can hold up to 15 characters for each name. You can create up to 10 alarm levels for each quantity.

Figure 6–3:Two alarms set up for the same quantity with different pickup and dropout set points

kW Demand

150

140

130

120

100

Alarm #43 Pick Up

 

Alarm #43 Drop Out

 

Alarm #26 Pick Up

 

Alarm #26 Drop Out

 

Time

Demand OK Approaching

Peak Demand

Below Peak Demand OK

Peak Demand

Exceeded

Demand

PLSD110156

kW Demand (default)

Alarm #26 kW Demand with pickup of 120 kWd, medium priority

kW Demand 150 kW (custom) Alarm #43 kW Demand with pickup of 150 kWd, high priority

Viewing Alarm Activity and History

1.Press ###: until ALARM is visible.

2.Press ALARM.

3.View the active alarm listed on the power meter display. If there are no active alarms, the screen reads, “NO ACTIVE ALARMS.”

4.If there are active alarms, press <--or -- > to view a different alarm.

5.Press HIST.

6.Press <--or -->to view a different alarm’s history.

7.Press 1; to return to the SUMMARY screen.

PLSD110258

54

© 2011 Schneider Electric. All Rights Reserved.

Page 60
Image 60