63230-500-225A2

PowerLogicTM Series 800 Power Meter

3/2011

 

 

Appendix A—Instrument Transformer Wiring: Troubleshooting Tables

Section II: 3-Wire System Troubleshooting

Section II—Case A

 

 

 

 

 

Symptoms: 3-Wire

Possible Causes

 

 

 

 

Currents and voltages approximately balanced

CT secondary leads are swapped (A-phase lead on C-phase terminal and

 

kW = near 0

vice versa).

 

kVAR = near 0

PT secondary leads are swapped (A-phase lead on C-phase terminal and

 

PF can be any value, probably fluctuating

vice versa).

 

 

 

 

 

Section II—Case B

 

 

 

 

 

Symptoms: 3-Wire

Possible Causes

 

 

 

 

 

Phase B current is 3 higher than A and C

 

 

 

(except in System Type 31).

 

 

kVA = about half of the expected magnitude

 

 

kW and kVAR can be positive or negative, less

One CT polarity is backwards.

 

 

than about half of the expected magnitude.

 

 

PF can be any value, probably a low leading

 

 

 

value.

 

 

 

 

Section II—Case C

 

 

 

 

 

Symptoms: 3-Wire

Possible Causes

 

 

 

 

 

VCA is 3 higher than VAB and VBC

 

 

kVA = about half of the expected magnitude

 

 

kW and kVAR can be positive or negative, less

One PT polarity is backwards.

 

 

than about half of the expected magnitude

 

 

PF can be any value, probably a low leading

 

 

 

value

 

 

 

 

Section II—Case D

 

 

 

 

 

Symptoms: 3-Wire

Possible Causes

 

 

 

 

kW = 0 or low, with magnitude less than kVAR

Either the two voltage leads are swapped OR the two current leads are

 

 

 

 

kVAR = positive or negative with magnitude of

swapped AND one instrument transformer has backwards polarity.

 

 

close to what is expected for kW

(look for VCA= 3 high or phase B current = 3 high)

 

kVA = expected magnitude

The power meter is metering a purely capacitive load (this is unusual); in

 

PF = near 0 up to about 0.7 lead

this case kW and kVAR will be positive and PF will be near 0 lead.

 

 

 

 

 

 

Section II—Case E

Symptoms: 3-Wire

Possible Causes

 

 

One phase current reads 0

The CT on the phase that reads 0 is short-circuited.

kVA = about 1/2 of the expected value

Less than 2% current (based on CT ratio) flowing through the CT on the

 

kW, kVAR, and power factor can be positive or

phase that reads 0.

 

negative of any value

 

 

 

 

© 2011 Schneider Electric All Rights Reserved

75

Page 83
Image 83
Schneider Electric PM850, PM870, PM820, PM810 manual Section II 3-Wire System Troubleshooting