63230-500-225A2

PowerLogicTM Series 800 Power Meter

3/2011

Chapter 3—Operation

Lock Resets Setup

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ADVAN (advanced setup) is visible.

3.Press ADVAN.

4.Press ###: until LOCK is visible.

5.Press LOCK.

6.Select Y (yes) or N (no) to enable or disable resets for PK.DMD, ENERG, MN/MX, and

METER.

7.Press OK.

8.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

9.Press YES to save the changes.

Alarm Backlight Setup

PLSD110200

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ADVAN (advanced setup) is visible.

3.Press ADVAN.

4.Press ###: until BLINK is visible.

5.Press BLINK.

6.Enter ON or OFF.

7.Press OK.

8.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

9.Press YES to save the changes.

PLSD110215

Bar Graph Setup

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until ADVAN (advanced setup) is visible.

3.Press ADVAN.

4.Press ###: until BARGR is visible.

5.Press BARGR.

6.Press AMPS or PWR.

7.Select AUTO or MAN. If MAN is selected, press OK and enter the %CT*PT and KW (for PWR) or the %CT and A (for AMPS).

8.Press OK.

9.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

10.Press YES to save the changes.

PLSD110231