PowerLogicTM Series 800 Power Meter

 

63230-500-225A2

Appendix D—Advanced Power Quality Evaluations

 

 

3/2011

 

Table D–8: Voltage dip classifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duration (t) seconds

 

 

 

 

 

Depth (D) % Nominal

1 t < 3

3 t < 10

10 t < 20

20 t < 60

60 t < 180

Total

 

 

10 D < 15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 D < 30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 D < 45

 

 

 

 

 

 

 

 

45 D < 60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 D < 75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 D < 90

 

 

 

 

 

 

 

 

90 D < 99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can configure the number of allowable events per week for each range of Depth in registers 3920 – 3927. (Default = -32768 = Pass/Fail evaluation disabled.)

Detection of Interruptions of the Supply Voltage

The standard defines an interruption as voltage less than 1% of nominal voltage. Because some locations require a different definition, you can configure this value in register 3906. Interruptions are classified as “short” if duration 3 minutes or “long” otherwise. The PM850 and the PM870 classifies interruptions as shown in Table D–9.

Table D–9: Voltage interruptions

Duration (t) seconds

 

t < 1

1 t < 2

2t < 5

5 t <

10 t <

20 t <

60 t <

180 t <

600 t <

1200 t

 

 

 

 

10

20

60

180

600

1200

 

Total

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can configure the number of allowable short interruptions per year in register 3918 (Default = -32768 = Pass/Fail evaluation disabled). You can configure the number of allowable long interruptions per year in register 3919. (Default = -32768 = Pass/Fail evaluation disabled.)

Detecting and Classifying Temporary Power Frequency Over-voltages

As stated in EN50160, a temporary power frequency over-voltage generally appears during a fault in the electrical utility power distribution system or in a customer’s installation, and disappears when the fault is cleared. Usually, the over-voltage may reach the value of phase-to-phase voltage because of a shift of the neutral point of the three-phase voltage system.

Under certain circumstances, a fault occurring upstream from a transformer will produce temporary over-voltages on the low voltage side for the time during which the fault current flows. Such over-voltages will generally not exceed 1.5 kV rms.

Table D–10shows how the PM850 and the PM870 detect and classify the over-voltages for each phase voltage.

NOTE: Disturbance alarms are used to detect these events in the PM870. In the PM850, standard speed over-voltage alarms are used to detect these events.

Table D–10: Over-voltages

Duration (t) seconds

Magnitude (M) %

1

t < 3

3 t < 10

10 t < 20

20 t < 60

60 t < 180

Total

Nominal

 

 

 

 

 

 

 

110 < M 115

 

 

 

 

 

 

 

115 < M 130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130 < M 145

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

145 < M 160

 

 

 

 

 

 

 

160 < M 175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

175 < M 200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M > 200

 

 

 

 

 

 

 

Total

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can configure the number of allowable events per week for each range of magnitude in registers 3930 – 3937. (Default = -32768 = Pass/Fail evaluation disabled.)

98

© 2011 Schneider Electric. All Rights Reserved.

Page 106
Image 106
Schneider Electric PM810, PM870 Detection of Interruptions of the Supply Voltage, Table D-8 Voltage dip classifications