63230-500-225A2

PowerLogicTM Series 800 Power Meter

3/2011

Chapter 3—Operation

COMMS (Communications) Setup

NOTE: If you are using PowerLogic software to set up the power meter, it is recommended you set up the communications features first.

Refer to Table 3-1 for the meter’s default settings.

Table 3–1: Communications Default Settings

Communications Setting

Default

Protocol

MB.RTU (Modbus RTU)

 

 

Address

1

 

 

Baud Rate

9600

 

 

Parity

Even

 

 

The same procedure is used to program the settings for the COMMS, COMM 1, and

COMM 2 options.

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until COMMS (communications) is visible.

3.Press COMMS (communications).

4.Select the required protocol: MB.RTU (Modbus RTU), Jbus, MB. A.8 (Modbus ASCII 8 bits), MB. A.7 (Modbus ASCII 7 bits).

5.Press OK.

6.Enter the ADDR (power meter address).

7.Press OK.

8.Select the BAUD (baud rate).

9.Press OK.

10.Select the parity: EVEN, ODD, or NONE.

11.Press OK.

12.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

13.Press YES to save the changes.

PLSD110100

METER Setup

This feature allows the user to configure the CTs, PTs, system frequency, and system wiring method.

CTs Setup

1.Perform steps 1 through 5 of the SETUP MODE Access procedure on page 11.

2.Press ###: until METER is visible.

3.Press METER.

4.Press CT.

5.Enter the PRIM (CT primary) number.

6.Press OK.

7.Enter the SEC. (CT secondary) number.

8.Press OK.

9.At the SETUP MODE screen, continue programming additional setup features or press1; until you are asked to save changes.

10.Press YES to save the changes.

PLSD110106

© 2011 Schneider Electric. All Rights Reserved.

15

Page 21
Image 21
Schneider Electric PM820, PM870, PM810, PM850 manual Comms Communications Setup, Meter Setup, CTs Setup