PowerLogicTM Series 800 Power Meter

 

63230-500-225A2

Appendix D—Advanced Power Quality Evaluations

3/2011

 

Table D–11: PQ Advanced Evaluation System Configuration and Status Registers

 

 

 

 

 

 

Register

Number

Description

 

 

3906

1

Definition of Interruption (EN50160 only)

 

 

0 – 10% Nominal (default = 1)

 

 

 

 

 

 

 

 

 

 

 

3907

1

Allowable Range of Slow Voltage Variations (EN50160 only)

 

 

1 – 20% Nominal (default = 10)

 

 

 

 

 

 

 

 

 

 

 

3908

1

Reserved

 

 

 

 

 

 

 

3909

1

Reserved

 

 

 

 

 

 

 

 

 

Bitmap of active evaluations

 

 

 

 

Bit 00 – Summary bit – at least one EN50160 evaluation is active

 

 

 

 

Bit 01 – Frequency

 

 

 

 

Bit 02 – Supply voltage variations

 

 

 

 

Bit 03 – Magnitude of rapid voltage changes

 

 

 

 

Bit 04 – Not used

 

 

 

 

Bit 05 – Supply voltage dips

 

 

 

 

Bit 06 – Short interruptions of the supply voltage

 

 

3910

1

Bit 07 – Long interruptions of the supply voltage

 

 

 

 

Bit 08 – Temporary power frequency over-voltages

 

 

 

 

Bit 09 – Not used

 

 

 

 

Bit 10 – Supply voltage unbalance

 

 

 

 

Bit 11 – Harmonic voltage

 

 

 

 

Bit 12 – THD

 

 

 

 

Bit 13 – Not used

 

 

 

 

Bit 14 – Not used

 

 

 

 

Bit 15 – Not used

 

 

 

 

 

 

 

 

 

Bitmap of evaluation status summary

 

 

 

 

Bit 00 – Summary bit – at least one EN50160 evaluation has failed.

 

 

 

 

Bit 01 – Frequency

 

 

 

 

Bit 02 – Supply voltage variations

 

 

 

 

Bit 03 – Magnitude of rapid voltage changes

 

 

 

 

Bit 04 – Not used

 

 

 

 

Bit 05 – Supply voltage dips

 

 

 

 

Bit 06 – Short interruptions of the supply voltage

 

 

3911

1

Bit 07 – Long interruptions of the supply voltage

 

 

 

 

Bit 08 – Temporary power frequency over-voltages

 

 

 

 

Bit 09 – Not used

 

 

 

 

Bit 10 – Supply voltage unbalance

 

 

 

 

Bit 11 – Harmonic voltage

 

 

 

 

Bit 12 – THD

 

 

 

 

Bit 13 – Not used

 

 

 

 

Bit 14 – Not used

 

 

 

 

Bit 15 – Not used

 

 

 

 

 

 

 

3912

2

Count of 10-second intervals present year

 

 

 

 

 

 

 

3914

2

Count of 10-second intervals this week

 

 

 

 

 

 

 

3916

1

Count of 10-minute intervals this week

 

 

 

 

 

 

 

3917

1

Number of allowable rapid voltage changes per week

 

 

Default = -32768 = Pass/Fail evaluation disabled

 

 

 

 

 

 

 

 

 

 

 

3918

1

Number of allowable short interruptions per year

 

 

Default = -32768 = Pass/Fail evaluation disabled

 

 

 

 

 

 

3919

1

Number of allowable long interruptions per year

 

 

Default = -32768 = Pass/Fail evaluation disabled

 

 

 

 

 

 

 

 

 

 

 

3920

8

Number of allowable voltage dips per week for each range of Depth

 

 

Default = -32768 = Pass/Fail evaluation disabled

 

 

 

 

 

 

 

 

 

 

 

3930

8

Number of allowable over-voltages per week for each range of Magnitude

 

 

Default = -32768 = Pass/Fail evaluation disabled

 

 

 

 

 

100

© 2011 Schneider Electric. All Rights Reserved.

Page 108