Chapter 6—Alarms

Table 6–5: List of Default Basic Alarms by Alarm Number

Alarm

Number

Alarm Description

Abbreviated

Display Name

Test

Register

Units

Scale

Group

Alarm Type

Standard Speed Alarms (1 Second)

01

Over Current Phase A

Over Ia

1100

Amperes

A

010

 

 

 

 

 

 

 

02

Over Current Phase B

Over Ib

1101

Amperes

A

010

 

 

 

 

 

 

 

03

Over Current Phase C

Over Ic

1102

Amperes

A

010

 

 

 

 

 

 

 

04

Over Current Neutral

Over In

1103

Amperes

B

010

 

 

 

 

 

 

 

05

Current Unbalance, Max

I Unbal Max

1110

Tenths %

010

 

 

 

 

 

 

 

06

Current Loss

Current Loss

3262

Amperes

A

053

 

 

 

 

 

 

 

07

Over Voltage Phase A–N

Over Van

1124

Volts

D

010

 

 

 

 

 

 

 

08

Over Voltage Phase B–N

Over Vbn

1125

Volts

D

010

 

 

 

 

 

 

 

09

Over Voltage Phase C–N

Over Vcn

1126

Volts

D

010

 

 

 

 

 

 

 

10

Over Voltage Phase A–B

Over Vab

1120

Volts

D

010

 

 

 

 

 

 

 

11

Over Voltage Phase B–C

Over Vbc

1121

Volts

D

010

 

 

 

 

 

 

 

12

Over Voltage Phase C–A

Over Vca

1122

Volts

D

010

 

 

 

 

 

 

 

13

Under Voltage Phase A

Under Van

1124

Volts

D

020

 

 

 

 

 

 

 

14

Under Voltage Phase B

Under Vbn

1125

Volts

D

020

 

 

 

 

 

 

 

15

Under Voltage Phase C

Under Vcn

1126

Volts

D

020

 

 

 

 

 

 

 

16

Under Voltage Phase A–B

Under Vab

1120

Volts

D

020

 

 

 

 

 

 

 

17

Under Voltage Phase B–C

Under Vbc

1121

Volts

D

020

 

 

 

 

 

 

 

18

Under Voltage Phase C–A

Under Vca

1122

Volts

D

020

 

 

 

 

 

 

 

19

Voltage Unbalance L–N, Max

V Unbal L-N Max

1136

Tenths %

010

 

 

 

 

 

 

 

20

Voltage Unbalance L–L, Max

V Unbal L-L Max

1132

Tenths %

010

 

 

 

 

 

 

 

21

Voltage Loss (loss of A,B,C, but

Voltage Loss

3262

Volts

D

052

 

not all)

 

 

 

 

 

22

Phase Reversal

Phase Rev

3228

051

 

 

 

 

 

 

 

23

Over kW Demand

Over kW Dmd

2151

kW

F

011

 

 

 

 

 

 

 

24

Lagging true power factor

Lag True PF

1163

Thousandths

055

 

 

 

 

 

 

 

25

Over THD of Voltage Phase A–N

Over THD Van

1207

Tenths %

010

 

 

 

 

 

 

 

26

Over THD of Voltage Phase B–N

Over THD Vbn

1208

Tenths %

010

 

 

 

 

 

 

 

27

Over THD of Voltage Phase C–N

Over THD Vcn

1209

Tenths %

010

 

 

 

 

 

 

 

28

Over THD of Voltage Phase A–B

Over THD Vab

1211

Tenths %

010

 

 

 

 

 

 

 

29

Over THD of Voltage Phase B–C

Over THD Vbc

1212

Tenths %

010

 

 

 

 

 

 

 

30

Over THD of Voltage Phase C–A

Over THD Vca

1213

Tenths %

010

 

 

 

 

 

 

 

31

Over kVA Demand

Over kVA Dmd

2181

kVA

F

011

 

 

 

 

 

 

 

32

Over kW Total

Over kW Total

1143

kW

F

011

 

 

 

 

 

 

 

33

Over kVA Total

Over kVA Total

1151

kVA

F

011

 

 

 

 

 

 

 

34-40

Reserved for additional analog

alarms

 

 

 

 

 

 

34-40

Reserved for custom alarms.

 

 

 

 

 

 

 

Digital

 

 

 

 

 

 

 

 

 

 

 

 

 

01

End of incremental energy

End Inc Enr Int

N/A

070

interval

 

 

 

 

 

 

02

End of power demand interval

End Dmd Int

N/A

070

03

Power up/Reset

Pwr Up/Reset

N/A

070

04

Digital Input OFF/ON

DIG IN S02

2

060

05-12

Reserved for additional digital

alarms

 

 

 

 

 

 

05-12

Reserved for custom alarms

 

 

 

 

 

 

 

Scale groups are described in Table 6–2 on page 49 .

Alarm types are described in Table 6–6 on page 52 .

Additional analog and digital alarms require a corresponding I/O module to be installed.