PowerLogicTM Series 800 Power Meter

63230-500-225A2

Chapter 6—Alarms

3/2011

Table 6–6: Alarm Types

Type

Description

Operation

Standard Speed

 

 

If the test register value exceeds the setpoint long enough to satisfy the pickup

010

Over Value Alarm

delay period, the alarm condition will be true. When the value in the test register

falls below the dropout setpoint long enough to satisfy the dropout delay period,

 

 

the alarm will drop out. Pickup and dropout setpoints are positive, delays are in

 

 

seconds.

 

 

If the absolute value in the test register exceeds the setpoint long enough to

 

 

satisfy the pickup delay period, the alarm condition will be true. When absolute the

011

Over Power Alarm

value in the test register falls below the dropout setpoint long enough to satisfy the

 

 

dropout delay period, the alarm will drop out. Pickup and dropout setpoints are

 

 

positive, delays are in seconds.

 

 

If the absolute value in the test register exceeds the setpoint long enough to

 

Over Reverse

satisfy the pickup delay period, the alarm condition will be true. When absolute the

012

value in the test register falls below the dropout setpoint long enough to satisfy the

Power Alarm

dropout delay period, the alarm will drop out. This alarm will only hold true for

 

 

 

reverse power conditions. Positive power values will not cause the alarm to occur.

 

 

Pickup and dropout setpoints are positive, delays are in seconds.

 

 

If the test register value is below the setpoint long enough to satisfy the pickup

020

Under Value Alarm

delay period, the alarm condition will be true. When the value in the test register

rises above the dropout setpoint long enough to satisfy the dropout delay period,

 

 

the alarm will drop out. Pickup and dropout setpoints are positive, delays are in

 

 

seconds.

 

 

If the absolute value in the test register is below the setpoint long enough to

021

Under Power Alarm

satisfy the pickup delay period, the alarm condition will be true. When the absolute

value in the test register rises above the dropout setpoint long enough to satisfy

 

 

the dropout delay period, the alarm will drop out. Pickup and dropout setpoints are

 

 

positive, delays are in seconds.

 

 

The phase reversal alarm will occur whenever the phase voltage waveform

051

Phase Reversal

rotation differs from the default phase rotation. The ABC phase rotation is

assumed to be normal. If a CBA phase rotation is normal, the user should

 

 

reprogram the power meter’s phase rotation ABC to CBA phase rotation. The

 

 

pickup and dropout setpoints for phase reversal do not apply.

 

 

The phase loss voltage alarm will occur when any one or two phase voltages (but

 

 

not all) fall to the pickup value and remain at or below the pickup value long

052

Phase Loss, Voltage

enough to satisfy the specified pickup delay. When all of the phases remain at or

above the dropout value for the dropout delay period, or when all of the phases

 

 

 

 

drop below the specified phase loss pickup value, the alarm will drop out. Pickup

 

 

and dropout setpoints are positive, delays are in seconds.

 

 

The phase loss current alarm will occur when any one or two phase currents (but

 

 

not all) fall to the pickup value and remain at or below the pickup value long

053

Phase Loss, Current

enough to satisfy the specified pickup delay. When all of the phases remain at or

above the dropout value for the dropout delay period, or when all of the phases

 

 

 

 

drop below the specified phase loss pickup value, the alarm will drop out. Pickup

 

 

and dropout setpoints are positive, delays are in seconds.

 

 

The leading power factor alarm will occur when the test register value becomes

 

 

more leading than the pickup setpoint (such as closer to 0.010) and remains more

 

 

leading long enough to satisfy the pickup delay period. When the value becomes

 

 

equal to or less leading than the dropout setpoint, that is 1.000, and remains less

054

Leading Power Factor

leading for the dropout delay period, the alarm will drop out. Both the pickup

 

 

setpoint and the dropout setpoint must be positive values representing leading

 

 

power factor. Enter setpoints as integer values representing power factor in

 

 

thousandths. For example, to define a dropout setpoint of 0.5, enter 500. Delays

 

 

are in seconds.

 

 

The lagging power factor alarm will occur when the test register value becomes

 

 

more lagging than the pickup setpoint (such as closer to –0.010) and remains

 

 

more lagging long enough to satisfy the pickup delay period. When the value

055

Lagging Power Factor

becomes equal to or less lagging than the dropout setpoint and remains less

lagging for the dropout delay period, the alarm will drop out. Both the pickup

 

 

setpoint and the dropout setpoint must be positive values representing lagging

 

 

power factor. Enter setpoints as integer values representing power factor in

 

 

thousandths. For example, to define a dropout setpoint of –0.5, enter 500. Delays

 

 

are in seconds.

Digital

 

 

 

 

The digital input transition alarms will occur whenever the digital input changes

060

Digital Input On

from off to on. The alarm will dropout when the digital input changes back to on

 

 

from off. The pickup and dropout setpoints and delays do not apply.

 

 

The digital input transition alarms will occur whenever the digital input changes

061

Digital Input Off

from on to off.The alarm will dropout when the digital input changes back to off

 

 

from on. The pickup and dropout setpoints and delays do not apply.

 

 

This is a internal signal from the power meter and can be used, for example, to

070

Unary

alarm at the end of an interval or when the power meter is reset. Neither the

 

 

pickup and dropout delays nor the setpoints apply.

52

© 2011 Schneider Electric. All Rights Reserved.

Page 58
Image 58
Schneider Electric PM810, PM870, PM820, PM850 manual Standard Speed