11. Modbus TCP server
11. 3. Ethernet card parameters
Comments:
•Parameters on 2 words are double words (low order in address word n, high order in address word n+1).
•Parameters 60 019 to 60 043 and 60 066 to 60 068 can be accessed in both read and write mode. They can be reset using a write operation.
•The current IP addresses (60006 to 60017) are the ones displayed on the terminal. The EEPROM IP addresses (60075 to 60079) are the ones used by the card.
Address | Size | Description | Access | Possible values, comments |
| (in words) |
|
|
|
60 000 | 6 | MAC address | R | |
|
|
|
| 00: 60 000 |
|
|
|
| 80: 60 001 |
|
|
|
| F4: 60 002 |
|
|
|
| 80: 60 003 |
|
|
|
| xx: 60 004 |
|
|
|
| yy: 60 005 |
|
|
|
|
|
60 006 | 4 | Current value of IP Address | R/W | IPC1.IPC2.IPC3.IPC4 |
|
| [IP card] |
| IPC1: 60 006 |
|
|
|
| IPC2: 60 007 |
|
|
|
| IPC3: 60 008 |
|
|
|
| IPC4: 60 009 |
60 010 | 4 | Current value of Subnet mask | R/W | IPM1.IPM2.IPM3.IPM4 |
|
| [IP Mask] |
| IPM1: 60 010 |
|
|
|
| IPM2: 60 011 |
|
|
|
| IPM3: 60 012 |
|
|
|
| IPM4: 60 013 |
|
|
|
|
|
60 014 | 4 | Current value of Gateway Address | R/W | IPG1.IPG2.IPG3.IPG4 |
|
| [IP Gate] |
| IPG1: 60 014 |
|
|
|
| IPG2: 60 015 |
|
|
|
| IPG3: 60 016 |
|
|
|
| IPG4: 60 017 |
60 018 | 1 | Transmission speed | R | = 0: Speed not defined |
|
| [Bit rate] (bdr) |
| = 10: 10 Mbps |
|
|
|
| = 100: 100 Mbps |
60 019 | 2 | OK transmission counter | R/W |
|
60 021 | 1 | R/W |
| |
60 022 | 1 | Late collision counter | R/W |
|
60 023 | 1 | Buffer (Tx) error counter | R/W |
|
60 024 | 2 | OK reception counter | R/W |
|
60 026 | 1 | CRC error counter | R/W |
|
60 027 | 1 | Frame error counter | R/W |
|
60 028 | 1 | Buffer (Rx) error counter | R/W |
|
60 029 | 1 | Collision counter | R/W |
|
60 030 | 1 | Multiple collision counter | R/W |
|
60 031 | 1 | OverRun counter | R/W |
|
60 032 | 2 | Sent Modbus TCP message counter | R/W | IO Scanning messages not included |
60 034 | 2 | Received Modbus TCP message counter | R/W | IO Scanning messages not included |
60 036 | 1 | Modbus TCP message error counter | R/W | IO Scanning messages not included |
60 037 | 2 | Sent IO Scanning message counter | R/W |
|
60 039 | 2 | Received IO Scanning message counter | R/W |
|
60 041 | 1 | IO Scanning message error counter | R/W |
|
60 042 | 1 | Active traffic (msg/s) | R/W |
|
60 043 | 1 | Max. traffic (msg/s) | R/W |
|
60 044 | 1 | Number of active TCP connections | R | 8 maximum |
32