11. Modbus TCP server

11. 3. Ethernet card parameters

Comments:

Parameters on 2 words are double words (low order in address word n, high order in address word n+1).

Parameters 60 019 to 60 043 and 60 066 to 60 068 can be accessed in both read and write mode. They can be reset using a write operation.

The current IP addresses (60006 to 60017) are the ones displayed on the terminal. The EEPROM IP addresses (60075 to 60079) are the ones used by the card.

Address

Size

Description

Access

Possible values, comments

 

(in words)

 

 

 

60 000

6

MAC address

R

00-80-F4-80-xx-yy

 

 

 

 

00: 60 000

 

 

 

 

80: 60 001

 

 

 

 

F4: 60 002

 

 

 

 

80: 60 003

 

 

 

 

xx: 60 004

 

 

 

 

yy: 60 005

 

 

 

 

 

60 006

4

Current value of IP Address

R/W

IPC1.IPC2.IPC3.IPC4

 

 

[IP card] (IPC-)

 

IPC1: 60 006

 

 

 

 

IPC2: 60 007

 

 

 

 

IPC3: 60 008

 

 

 

 

IPC4: 60 009

60 010

4

Current value of Subnet mask

R/W

IPM1.IPM2.IPM3.IPM4

 

 

[IP Mask] (IPM-)

 

IPM1: 60 010

 

 

 

 

IPM2: 60 011

 

 

 

 

IPM3: 60 012

 

 

 

 

IPM4: 60 013

 

 

 

 

 

60 014

4

Current value of Gateway Address

R/W

IPG1.IPG2.IPG3.IPG4

 

 

[IP Gate] (IPG-)

 

IPG1: 60 014

 

 

 

 

IPG2: 60 015

 

 

 

 

IPG3: 60 016

 

 

 

 

IPG4: 60 017

60 018

1

Transmission speed

R

= 0: Speed not defined

 

 

[Bit rate] (bdr)

 

= 10: 10 Mbps

 

 

 

 

= 100: 100 Mbps

60 019

2

OK transmission counter

R/W

 

60 021

1

Store-and-forward transmission counter

R/W

 

60 022

1

Late collision counter

R/W

 

60 023

1

Buffer (Tx) error counter

R/W

 

60 024

2

OK reception counter

R/W

 

60 026

1

CRC error counter

R/W

 

60 027

1

Frame error counter

R/W

 

60 028

1

Buffer (Rx) error counter

R/W

 

60 029

1

Collision counter

R/W

 

60 030

1

Multiple collision counter

R/W

 

60 031

1

OverRun counter

R/W

 

60 032

2

Sent Modbus TCP message counter

R/W

IO Scanning messages not included

60 034

2

Received Modbus TCP message counter

R/W

IO Scanning messages not included

60 036

1

Modbus TCP message error counter

R/W

IO Scanning messages not included

60 037

2

Sent IO Scanning message counter

R/W

 

60 039

2

Received IO Scanning message counter

R/W

 

60 041

1

IO Scanning message error counter

R/W

 

60 042

1

Active traffic (msg/s)

R/W

 

60 043

1

Max. traffic (msg/s)

R/W

 

60 044

1

Number of active TCP connections

R

8 maximum

32