11. Modbus TCP server

11. 1. Modbus TCP frames

Modbus TCP frames consist of a header and a Modbus request.

Header format:

Byte

Description

 

Comments

0

Transaction identifier

high order

 

1

low order

 

 

 

2

Protocol identifier

high order

This identifier always equals 0.

3

low order

 

 

4

Length of data

high order

Number of bytes in the Modbus request +1. The frame length is always less than

5

low order

256 bytes, the value of the significant byte therefore equals 0.

 

6

Destination identifier (Unit ID)

 

 

7

Modbus request function code

 

 

The frame header returned by the Altivar 71 server is identical to that of the frame sent by the client.

11. 2. Drive Modbus servers

The destination identifier (Unit ID) is used to access 4 drive Modbus TCP servers:

Unit ID

Modbus TCP server

Accessible parameters

0

Variable speed drive

See the Altivar 71 Communication parameters Manual.

251, AMOC

Ethernet card

See the “Ethernet card parameters” section.

252, AMOA

Controller Inside card

2048 words (%MW0 to %MW2047).

255

IO Scanner

See the “IO Scanner” section.