8. Configuration

8. 2. Configuring IP addresses

b Assigning IP addresses

The drive needs 3 IP addresses:

The drive IP address.

The subnet mask.

The gateway IP address (not always required).

Note: Some controllers, such as Prosoft® and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This address must be set in menu 1.9 of the drive, as well as in the software for the master device.

These IP addresses can be entered:

Using the integrated display terminal.

Using the graphic display terminal.

Using the PowerSuite software workshop.

They can be provided by:

A BOOTP server (correspondence between the MAC address and the IP addresses).

A DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).

If an IP address other than 0.0.0.0 has been entered using the display terminal or the PowerSuite software workshop, assignment using a server is disabled.

The BOOTP service is enabled:

When no IP address other than 0.0.0.0 has been entered and

The FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).

The DHCP service is enabled:

When no IP address other than 0.0.0.0 has been entered and

The FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).

 

Power-up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initialization

 

 

An address has been entered

 

 

 

[IP card] <> 0.0.0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No address has

been entered

 

 

 

[IP card] = 0.0.0.0

 

 

Static

addressing

Dynamic

addressing

[FDR validation] = [No]

BOOTP

[FDR validation] = [Yes]

FDR

[DEVICE NAME] blank

[DEVICE NAME] has been

entered

DHCP

17

Page 17
Image 17
Schneider Electric VW3A3310d user manual Configuring IP addresses, Assigning IP addresses, Power-up Initialization