9. Diagnostics

9. 2. Available information

In addition to the LEDs, the table below summarizes the diagnostic information available by various means.

Functions

Graphic display

Integrated display

PowerSuite software

Standard

 

 

terminal

terminal

workshop

web server

Control-signal diagnostics

 

 

 

 

Control word

p

p

p

p

Setpoint

Active channel

 

 

 

 

Etc.

 

 

 

 

 

 

 

 

 

Communication diagnostics

 

 

 

 

Transmission counter

 

 

p

p

Reception counter

 

 

Collision counter

 

 

 

 

Etc.

 

 

 

 

9. 3. Monitoring the control

On the graphic display terminal only, the [1.2 - MONITORING] menu, [COMMUNICATION MAP] submenu can be used to display control signal diagnostic information between the drive and the Ethernet PLC:

Active command channel

Value of control word used to send a command to the drive (hexadecimal format)

Active setpoint channel

Value of frequency setpoint (unit 0.1 Hz) used to control the drive

Value of status word (hexadecimal format)

Values of the four monitored words selected by the user. The address and display format of these parameters can be configured in the [6 - MONITORING CONFIG.] menu, [6.3 - COM. MAP CONFIG.] submenu (see “Configuration” section on page 16).

The value of a monitored word is equal to ----- if:

-Monitoring has not been activated (address equal to W0)

-The parameter is protected

-The parameter is not known (e.g., W3200)

RUN

NET

+50.00 Hz 80A

 

 

 

COMMUNICATION MAP

 

 

 

Command Channel

:

Com. card

Cmd value

 

:

000FHex

Channel ref. active

:

Com. card

Frequency ref.

 

:

500.0Hz

Status word

 

:

8627Hex

 

Code

 

 

Quick

 

 

 

 

 

 

 

W3204

 

:

53

 

W3205

 

:

725

 

W7132

 

:

0000Hex

W0

 

:

-----

 

 

 

 

 

Hex

 

 

COM. SCANNER INPUT MAP

Communication scanner:

 

COM SCAN OUTPUT MAP

 

CMD. WORD IMAGE

 

Use not recommended for Ethernet

 

for performance reasons

 

FREQ. REF. WORD MAP

 

 

Control word from Ethernet

 

MODBUS NETWORK DIAG

 

MODBUS HMI DIAG

[COM. card cmd.] (CMd3)

 

 

 

 

 

CANopen MAP

Frequency setpoint from Ethernet

 

SCANNER CARD PROG.

[Com. card ref.] (LFr3)

 

 

27

Page 27
Image 27
Schneider Electric VW3A3310d user manual Available information, Monitoring the control, Integrated display