7. Ethernet menu

 

 

Code

 

Description

 

 

 

 

 

 

(FdrA)

 

M [FDR Action]

 

 

 

 

 

 

 

 

FDR service command

 

 

 

 

 

 

Type:

Command (read and write)

 

 

 

 

 

 

Possible

[IDLE] (IdLE): No command.

 

 

 

 

 

 

values:

[SAVE] (SAUE): Command: save.

 

 

 

 

 

 

 

[REST] (rESt): Command: download.

 

 

 

 

 

 

 

[DEL] (dEL): Command: delete.

 

 

 

 

 

 

 

The command remains displayed during the action then reverts to the value [IDLE] (IdLE).

 

 

 

 

 

 

Default value:

[IDLE] (IdLE)

 

 

 

 

(FdrS)

 

M [FDR autosave]

 

 

 

 

 

 

 

 

Enable periodic saving of the FDR service

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

Possible

[No] (nO): Automatic saving disabled.

 

 

 

 

 

 

values:

[Yes] (YES): Automatic saving enabled.

 

 

 

 

 

 

Default value:

[No] (nO)

 

 

 

 

(Fdrt)

 

M [FDR t.autosave]

 

 

 

 

 

 

 

 

Interval for periodic saving of the FDR service

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

Possible

[2] (2) to [9999] (9999): 2 min to 9999 min.

 

 

 

 

 

 

values:

 

 

 

 

 

 

 

 

Default value:

[10] (10)

 

 

 

 

(FdrE)

 

M [FDR state]

 

 

 

 

 

 

 

 

FDR service state

 

 

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

Possible

[IDLE] (IdLE): “Idle”.

 

 

 

 

 

 

values:

[INIT] (INIt): Initialization.

 

 

 

 

 

 

 

[CONF] (CONF): Configuration.

 

 

 

 

 

 

 

[RDY] (rdY): Ready.

 

 

 

 

 

 

 

[GET] (GEt): Download the current configuration.

 

 

 

 

 

 

 

[SET] (SEt): Save the current configuration.

 

 

 

 

 

 

 

[APP] (APP): Write the FDR server configuration to the drive.

 

 

 

 

 

 

 

[OPE] (OPE): Operational.

 

 

 

 

 

 

 

[UCFG] (UCFG): Not configured.

 

 

 

 

 

 

Default value:

[IDLE] (IdLE)

 

 

 

 

(Fdrd)

 

M [FDR Error Code]

 

 

 

 

 

 

 

FDR service status code

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

Possible

[0] (0): No communication interruption

 

 

 

 

 

 

values:

[2] (2): The FDR configuration file is not compatible with the drive type

 

 

 

 

 

 

 

 

(example: the drive is not the same rating as that defined in the FDR file).

 

 

 

 

 

 

 

[3] (3): Error reading the FDR configuration file on the server.

 

 

 

 

 

 

 

[4] (4): Error writing the FDR configuration file to the server.

 

 

 

 

 

 

 

[7] (7): Time-out for receipt of the FDR configuration file from the server.

 

 

 

 

 

 

 

[9] (9): Duplication of IP address.

 

 

 

 

 

 

 

[12] (12): The FDR configuration file is missing.

 

 

 

 

 

 

Default value:

[0] (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

Page 15
Image 15
Schneider Electric VW3A3310d user manual FdrA, FdrS, Fdrt, FdrE, Fdrd