15
7. Ethernet menu
Code Description
(FdrA)M [FDR Action]
FDR service command
Type: Command (read and write)
Possible
values:
[IDLE] (IdLE): No command.
[SAVE] (SAUE): Command: save.
[REST] (rESt): Command: download.
[DEL] (dEL): Command: delete.
The command remains displayed during the action then reverts to the value [IDLE] (IdLE).
Default value: [IDLE] (IdLE)
(FdrS)M [FDR autosave]
Enable periodic saving of the FDR service
Type: Configuration (read and write)
Possible
values:
[No] (nO): Automatic saving disabled.
[Yes] (YES): Automatic saving enabled.
Default value: [No] (nO)
(Fdrt)M [FDR t.autosave]
Interval for periodic saving of the FDR service
Type: Configuration (read and write)
Possible
values:
[2] (2) to [9999] (9999): 2 min to 9999 min.
Default value: [10] (10)
(FdrE)M [FDR state]
FDR service state
Type: Display (read-only)
Possible
values:
[IDLE] (IdLE): “Idle”.
[INIT] (INIt): Initialization.
[CONF] (CONF): Configuration.
[RDY] (rdY): Ready.
[GET] (GEt): Download the current configuration.
[SET] (SEt): Save the current configuration.
[APP] (APP): Write the FDR server configuration to the drive.
[OPE] (OPE): Operational.
[UCFG] (UCFG): Not configured.
Default value: [IDLE] (IdLE)
(Fdrd)M [FDR Error Code]
FDR service status code
Type: Display (read-only)
Possible
values:
[0] (0): No communication interruption
[2] (2): The FDR configuration file is not compatible with the drive type
(example: the drive is not the same rating as that defined in the FDR file).
[3] (3): Error reading the FDR configuration file on the server.
[4] (4): Error writing the FDR configuration file to the server.
[7] (7): Time-out for receipt of the FDR configuration file from the server.
[9] (9): Duplication of IP address.
[12] (12): The FDR configuration file is missing.
Default value: [0] (0)