13. FDR service

M Download the IP addresses

Connect the drive and the FDR server (PLC) to the Ethernet network.

The server downloads the IP addresses to the Ethernet card.

Check that the operation has proceeded correctly:

• The “STS” LED should be on.

You can also check, in the [1.9 - COMMUNICATION] (COM-)menu, [ETHERNET] (EtH-)submenu whether the [IP card] (IPC1) (IPC2) (IPC3) (IPC4), [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4) and [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4) parameters have values other than [0.0.0.0] (0) (0) (0) (0).

M Save the drive configuration parameters in the FDR server

• Configure the drive parameters.

In the [1.9 - COMMUNICATION] (COM-)menu, [ETHERNET] (EtH-)submenu:

Specify that the drive configuration is to be downloaded from the FDR server on each power-up: [FDR Local Config.] (LCFG) = [No] (nO).

Send a save command to the FDR server: [FDR Action] (FdrA) = [SAVE] (SAUE).

After execution of the command, the [FDR Action] (FdrA) parameter reverts to the value [IDLE] (IdLE).

M Check that the system is operational

Check that the operation has proceeded correctly:

The “STS” LED should be on.

The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).

If the save operation has not been successful, the card triggers a drive status [External fault com.] (EPF2).

b Replacing a drive

Procedure:

Configure the drive.

Turn off the drive.

Connect the drive to the network.

Check that the drive is operational.

M Configure the drive

In the [1.9 - COMMUNICATION] (COM-)menu, [ETHERNET] (EtH-)submenu:

Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).

Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).

Specify that the drive configuration is to be downloaded from the FDR server on each power-up: [FDR Local Config.] (LCFG) = [No] (nO).

These configurations are the default values.

Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.

This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-)menu, set the level to [expert] (EPr).

M Turn the drive off and then back on again

Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken into account.

M Connect the drive to the network

M Check that the system is operational

Check that the operation has proceeded correctly:

The “STS” LED should be on.

The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).

If downloading has not been possible after a period of 2 min following assignment of the IP addresses, the card triggers a drive status [External fault com.] (EPF2).

45

Page 45
Image 45
Schneider Electric VW3A3310d user manual Replacing a drive, Download the IP addresses, Check that the system is operational