8. Configuration

b Command in CiA402 (Drivecom) profile via Ethernet and setpoint switching at the terminals

The command comes from Ethernet.

The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet and the terminals.

The command is in CiA402 profile.

Configure the following parameters:

 

 

 

 

Parameter

Value

Comment

Profile

Separate

The run commands are in CiA402 profile, the command and the setpoint

 

 

can come from different channels.

Setpoint 1 configuration

Network card

Setpoint 1 comes from Ethernet.

Setpoint 1B configuration

Analog input 1 on the terminals

Setpoint 1B comes from input AI1 on the terminals.

Setpoint switching

Input LI5

Input LI5 switches the setpoint (1 1B).

Command 1 configuration

Network card

Command 1 comes from Ethernet.

Command switching

Channel 1

Channel 1 is the command channel.

Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6

- COMMAND] (CtL-)

[Profile] (CHCF)

[Separate] (SEP)

 

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

 

[Cmd switching] (CCS)

[Ch1 active] (Cd1)

[1.7

APPLICATION FUNCT.] (FUn-)

[Ref.1B channel] (Fr1b)

[Ref. AI1] (AI1)

[REFERENCE SWITCH.]

 

 

[Ref 1B switching] (rCb)

[LI5] (LI5)

 

 