7. Ethernet menu

 

 

Code

 

Description

 

 

 

 

 

 

(IPP-)

 

b [IP Master]

 

 

 

 

(IPP1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPP2)

 

 

 

 

 

 

 

 

 

 

(IPP3)

 

 

IP address of the device that retains control

 

 

 

 

(IPP4)

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

 

 

Display (read-only) if the address is supplied by a DHCP server

 

 

 

 

 

 

 

Possible

 

• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.

 

 

 

 

 

 

 

values:

 

• If the value is [0.0.0.0] (0) (0) (0) (0), writing of the control word (CMd) is accepted

 

 

 

 

 

 

 

 

 

 

by the Ethernet card regardless of which device has sent it.

 

 

 

 

 

 

 

 

 

If the value is other than [0.0.0.0] (0) (0) (0) (0) only the device which has the IP address

 

 

 

 

 

 

 

 

 

 

[IP Master] is authorized to write the control word (CMd).

 

 

 

 

 

 

 

 

 

Note: This configuration also affects the type of communication monitoring.

 

 

 

 

 

 

 

Default value:

 

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPF-)

 

b [IP FDR]

 

 

 

 

 

 

(IPF1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPF2)

 

 

 

 

 

 

 

 

 

 

(IPF3)

 

 

IP address of the FDR server

 

 

 

 

(IPF4)

 

 

Type:

 

Display (read-only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible

 

• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.

 

 

 

 

 

 

 

values:

 

• If the value is [0.0.0.0] (0) (0) (0) (0), there is no server.

 

 

 

 

 

 

 

Default value:

 

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(ISA)

 

 

M [IO Scan.activ.]

 

 

 

 

 

 

 

 

 

 

Enable IO Scanner

 

 

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): IO Scanner disabled.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): IO Scanner enabled.

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

(tOUt)

 

 

M [time out]

 

 

 

 

 

 

 

 

 

 

Ethernet communication monitoring time out

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[0] (0): Monitoring disabled.

 

 

 

 

 

 

 

values:

 

[0.5 s] (0.5) to [60.0 s] (60.0): Time out value (unit: 0.1 s).

 

 

 

 

 

 

 

Default value:

 

[2.0 s] (2.0)

 

 

 

 

(FdrU)

 

 

M [FDR validation]

 

 

 

 

 

 

 

 

 

 

Enable FDR service

 

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): FDR service disabled.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): FDR service enabled.

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

(LCFG)

 

 

M [FDR Local Config.]

 

 

 

 

 

 

 

Selection of local or server configuration

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): The drive configuration is downloaded from an FDR server.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): The drive configuration is local and saved in a FDR server.

 

 

 

 

 

 

 

Default value:

 

[No] (nO)

 

 

 

 

(FdrF)

 

 

M [FDR Error Mgt.]

 

 

 

 

 

 

 

 

 

 

Enable FDR file error detection

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

In the event of a problem with the FDR file (missing or invalid):

 

 

 

 

 

 

 

values:

 

[No] (nO): The Ethernet card does not trigger an [FDR fault] (Fdrd).

 

 

 

 

 

 

 

 

 

[Yes] (YES): The Ethernet card triggers an [FDR fault] (Fdrd).

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 