11. Modbus TCP server
11. 6. “Write Single Register” (6) function
This Modbus request is used to write a given value (Preset Data) to the address supplied (Register Address).
Request format:
Byte | Meaning |
0Function Code = 16#06
1Register Address Hi
2Register Address Lo
3Preset Data Hi
4Preset Data Lo
Response format:
Byte | Meaning |
0Function Code = 16#06
1Register Address Hi
2Register Address Lo
3Preset Data Hi
4Preset Data Lo
Exception response format: |
|
| ||
|
|
| ||
Byte | Meaning | With the VW3A3310d Ethernet card | ||
0 | Function Code = 16#86 |
|
| |
|
| 01 | (Illegal Function) | |
1 | Exception Code | 02 | (Illegal Data Address) | |
03 | (Illegal Data Value) | |||
|
| |||
|
| 04 | (Illegal Response Length) | |
|
|
|
|
36