Schneider Electric VW3A3310d user manual Read Device Identification 43 = 16#2B function

Models: VW3A3310d

1 80
Download 80 pages 21.32 Kb
Page 39
Image 39

11. Modbus TCP server

11. 9. “Read Device Identification” (43 = 16#2B) function

Request format:

Byte

Meaning

With the VW3A3310d Ethernet card

 

0

Function Code = 16#2B

16#2B

 

1

Type of MEI

16#0E

 

 

 

16#01: Basic

 

2

Read Device ID code

16#02: Regular

 

 

 

16#03: Extended

 

3

Object ID

16#00

 

 

Response format:

 

 

 

 

 

 

 

 

 

Byte(s)

Meaning

With the VW3A3310d Ethernet card

0

Function code = 16#2B

16#2B

1

Type of MEI

16#0E

2

ReadDeviceId code

16#01

 

 

3

Degree of conformity

16#02

 

 

4

Number of additional frames

16#00 (a single frame)

5

Next object ID

16#00

 

 

6

Number of objects

3 for Basic

4 for Regular or Extended

 

 

7

Object no. 1 ID

16#00 = Vendor Name

8

Length of object no. 1 (A)

13

 

 

9…21

Value of object no. 1 (A ASCII characters)

“Telemecanique”

22

Object no. 2 ID

16#01 = Product Code

23

Length of object no. 2 (B)

11 (for the following example only)

24…23+B

Value of object no. 2 (B ASCII characters) (1)

Example: “ATV71HU15M3”

24+B

Object no. 3 ID

16#02 = Major.Minor Revision

25+B

Length of object no. 3 (C)

4

 

 

26+B…29+B

Value of object no. 3 (C ASCII characters)

Example: “0201” for version 2.1

30+B

Object no. 4 ID

16#06 = Application Name (2)

 

 

31+B

Length of object no. 4 (D)

8 (for the following example only)

for Regular and Extended

32+B…31+B+D

Value of object no. 4 (D ASCII characters) (1)

Example: “MACHINE 4”

 

 

(1)The length of this field is variable. Use the “Length of object no. X” field associated with it to determine the length.

(2)In the case of the drive, this data item corresponds to [DEVICE NAME].

The response to a “drive identification” request does not cause an exception response.

39

Page 39
Image 39
Schneider Electric VW3A3310d user manual Read Device Identification 43 = 16#2B function