8. Configuration

8. 5. Configuring the control

Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters Manual.

The following configurations are just some of the possibilities available.

b Control via Ethernet in I/O profile

The command and setpoint come from Ethernet.

The command is in I/O profile.

Configure the following parameters:

 

 

 

 

Parameter

Value

Comment

Profile

I/O profile

The run command is simply obtained by bit 0 of the control word.

Setpoint 1 configuration

Network card

The setpoint comes from Ethernet.

Command 1 configuration

Network card

The command comes from Ethernet.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

[Cmd channel 1] (Cd1)

[Com. opt card] (nEt)

b Control via Ethernet or the terminals in I/O profile

Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals.

The command is in I/O profile.

Configure the following parameters:

 

 

 

 

 

Parameter

Value

Comment

Profile

I/O profile

The run command is simply obtained by bit 0 of the control word.

Setpoint 1 configuration

Network card

Setpoint

1 comes from Ethernet.

Setpoint 1B configuration

Analog input 1 on the terminals

Setpoint

1B comes from input AI1 on the terminals.

Setpoint switching

Input LI5

Input LI5 switches the setpoint (1 1B).

Command 1 configuration

Network card

Command 1 comes from Ethernet.

Command 2 configuration

Terminals

Command 2 comes from the terminals.

Command switching

Input LI5

Input LI5 switches the command.

Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6

- COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

 

[Cmd channel 2] (Cd2)

[Terminals] (tEr)

 

 

[Cmd switching] (CCS)

[LI5] (LI5)

[1.7

APPLICATION FUNCT.] (FUn-)

[Ref.1B channel] (Fr1b)

[Ref. AI1] (AI1)

[REFERENCE SWITCH.]

 

 

[Ref 1B switching] (rCb)

[LI5] (LI5)

 

 