2. Meanings of LEDs on CC-Link compatible module
4
Troubleshooting
c CAUTION
Even if the LED displays indicate the normal communication state, there may be cases when communication with the master station PLC is not possible unless the initial data process is carried out. Always carry out the initial data process. (Refer to Chapter 3.)
|
|
| 2 | 3 |
|
| 0 | 1 |
|
| 4 |
|
|
|
| 5 | |
| 9 |
|
| ||
|
|
| 8 |
| 6 |
|
|
| 7 |
| |
|
| 1 | 2 | 3 | 4 |
RUN | 0 |
|
| 5 | |
9 |
|
| |||
0 | 1 | 2 | 3 | 6 | |
4 | |||||
|
|
| 8 | 7 |
|
ERRL | 9 |
|
| 5 | |
|
| 8 |
| 6 | |
|
| 7 |
| ||
|
|
|
|
| |
SD |
|
|
|
|
|
RD |
|
|
|
|
|
Front of the unit
The LEDs on the
RUN ERRL SD RD | Meaning |
Normal communication is taking place, but the CRC error occurs sometimes because of noise.
The settings have varied from the baud rate and station No. setting made when connected to the
A CRC error occurred in the received data, and a response cannot be made.
Normal communication
There is no data addressed to the local station.
Station No. setting illegal.
Communication speed setting illegal. (Unusable communication speed was specified.)
Polling response is being carried out, but a CRC error occurred in the refresh reception.
A CRC error occurred in the data addressed to the local station.
Data has not been initialized.
The local station is not set to a remote device station.
There is no data addressed to the local station or the data addressed to the local station cannot be received because of noise. An illegal communication speed was set. (It can be spefified but differs from the master station.)
Data cannot be received because of a line disconnection.
The power for communication has been cut off.
Communication with the master station was not possible when the power was turned ON.
Others | An improbable state |